F E AT U R E S - S P E C I F I C AT I O N S
E N V I R O N M E N TA L C O N T R O L S
E T R & Z R S E R I E S T H E R M O S TAT S
Industry Standards
UL Recognized Component
cUL Recognized Component
CE Recognized
CSA Rated
ETR202
ETR202F
ZR011
Applications
ETR202C and ETR202F
• Designed to provide air temperature
control and monitoring in switch
gear enclosures that are set up to
operate with heaters, fans, filter
ventilators, heat exchangers,
and/or signal transmitters.
• When the enclosure reaches the
pre-determined set point, tempera-
ture contacts in the thermostat are
activated and the fan or heater
automatically begins to operate.
• Thermostats prolong the life
expectancy of heaters and fans by
curtailing their operating hours and
also increase the working efficiency
of electrical components by expos-
ing them to fewer contaminants from
the surrounding environment.
ZR011
• The ZR011 houses two separate
thermostats, allowing the independent
control of heating and cooling or
other equipment. Both thermostats
offer wide adjustment ranges and
are color coded for easy function
recognition.
• Switching capacity:
NC: 10A resistive/2A inductive
@ 250 VAC
NO: 5A resistive/2A inductive
@ 250 VAC DC 30W
C ATA L O G
T E M P.
T E M P.
S W I T C H I N G
F O R P R O D U C T
D I M E N S I O N S
N U M B E R
S C A L E
R A N G E
T Y P E
H X W X D
E T R 2 0 2 F
F a h r e n h e i t
3 2 - 1 4 0 º F
N o r m a l l y C l o s e d
H e a t i n g
2 . 4 0 x 1 . 3 0 x 1 . 4 0 ( 6 0 x 3 3 x 3 5 )
E T R 2 0 2
C e l s i u s
0 - 6 0 º C
N o r m a l l y C l o s e d
H e a t i n g
2 . 4 0 x 1 . 3 0 x 1 . 4 0 ( 6 0 x 3 3 x 3 5 )
E T R 2 0 1 F
F a h r e n h e i t
3 2 - 1 4 0 º F
N o r m a l l y O p e n
C o o l i n g
2 . 4 0 x 1 . 3 0 x 1 . 4 0 ( 6 0 x 3 3 x 3 5 )
E T R 2 0 1
C e l s i u s
0 - 6 0 º C
N o r m a l l y O p e n
C o o l i n g
2 . 4 0 x 1 . 3 0 x 1 . 4 0 ( 6 0 x 3 3 x 3 5 )
Z R 0 1 1 F
F a h r e n h e i t
3 2 - 1 4 0 º F
N o r m a l l y C l o s e d /
H e a t i n g / C o o l i n g
2 . 6 0 x 2 . 0 0 x 1 . 8 0 ( 6 7 x 5 0 x 4 6 )
N o r m a l l y O p e n
Z R 0 1 1 C
C e l s i u s
0 - 6 0 º C
N o r m a l l y C l o s e d /
H e a t i n g / C o o l i n g
2 . 6 0 x 2 . 0 0 x 1 . 8 0 ( 6 7 x 5 0 x 4 6 )
N o r m a l l y O p e n
E T R & Z R S E R I E S T H E R M O S TAT S
Features
• Normally Closed Thermostat — For
the control of fan heaters and heaters
• Normally Open Thermostat — For the
control of cooling units, fans, filter
ventilators or switching, or signal
transmitters in the event of overheating
• Available in Fahrenheit or Celsius scale
• Thermostatic bi-metallic sensor element
• Easily installed by clip mounting on
35mm or 38mm DIN rails
• Housing made from gray flame
retardant UL94-VO plastic
• Connection: 2 pole terminal for max.
14 AWG
• Switching Difference (hysteresis):
12ºF (7ºC)
• Switching Capacity: 15 A (2) AC
120V, 10 A (2) AC 250V, 10A 12V
DC, 5A 24V DC
• Two thermostats in one unit
– one Normally Closed (NC)
and one Normally Open (NO)
– or two Normally Open (NO)
• Each with wide adjustable tem-
perature range
• Available with °F or °C scale
• DIN rail mountable
- WPFM Series WPFG Series WPFA Series WPF Series FILTER MATS Series EXHAUST FILTER Series FILTER FANS Series WAFMP Series ETF Series ZR Series ETR Series EGL Series WCR Series WHVL Series EHG Series WAFLT Series WAVK-SS Series WAVK Series WAGARD Series WAAXFN Series WPFBE Series WPFB Series Vortex Coolers Series Top-Mount Series 47 Series 38 Series 32 Series MM Series NP47 Series NP36 Series NP33 Series NP28 Series NP17 Series RP47 Series RP36 Series RP33 Series RP28 Series RP17 Series