Installation, Technical specifications - power wave, S350 – Lincoln Electric IM10007 POWER WAVE S350 User Manual
Page 8

A-1
INSTALLATION
POWER WAVE
®
S350
A-1
TECHNICAL SPECIFICATIONS - POWER WAVE
®
S350
RECOMMENDED INPUT WIRE AND FUSE SIZES
1
INPUT
VOLTAGE / PHASE/
FREQUENCY
200-208/1/50/60
200-208/3/50/60
230/1/50/60
230/3/50/60
380-415/1/50/60
380-415/3/50/60
460/1/50/60
460/3/50/60
575/1/50/60
575/3/50/60
TIME DELAY FUSE
OR BREAKER
2
AMPERAGE
80
50
80
45
50
30
45
25
35
20
NOTES
NOTE 4
NOTE 4
CORD SIZE
3
AWG SIZES
(mm
2
)
6 (13)
8 (10)
4 (16)
8 (10)
8 (10)
12 (4)
8 (10)
12 (4)
10 (6)
14 (2.5)
MAXIMUM
INPUT AMPERE RAT-
ING AND DUTY CYCLE
60A, 100%
39A, 40%
67A, 30%
35A, 40%
38A, 40%
19A, 40%
34A, 40%
17A, 40%
27A, 40%
14A, 40%
RATED OUTPUT
POWER SOURCE-INPUT VOLTAGE AND CURRENT
Model
K2823-1
Duty Cycle
40% rating
100% rating
300
Amps
29
Volts
350
Amps
31.5
Volts
320
Amps
30
Volts
INPUT
VOLTAGE / PHASE /
FREQUENCY
200-208/1/50/60
230/1/50/60
460/1/50/60
575/1/50/60
200-208/3/50/60
230/3/50/60
380-415/3/50/60
460/3/50/60
575/3/50/60
Input Amperes
(1 Phase in parenthesis)
39/35/20/17/14
(NA/65***/37/32/25)
30/28/16/14/11
(56/51/29/25/20)
Idle Power
300 Watts Max.
(fan on)
Power Factor @
Rated Output
.95
Input Voltage ± 10%
200-208/230/380-415/
460/575
50/60 Hz
1. Based on U.S. National electrical Code
2. Also called " inverse time" or "thermal / magnetic" circuit breakers; circuit breakers that have a delay in trip-
ping action that decreases as the magnitude of the current increases
3. Type SO cord or similar in 30° C ambient
4. When operating on these inputs, the line cord should be changed to an input conductor of 6 AWG or larger.
*** On 230 Volt / 1 phase inputs the max. rating is at a duty cycle of 30%, except for GTAW processes.
GMAW
40%***
60%
60%
100%
300 Amps / 29 Volts
250
Amps
30
Volts
325
Amps
33
Volts
275
Amps
31
Volts
SMAW
40%***
100%
250 Amps / 30 Volts
300
Amps
22 Volts
350
Amps
24 Volts
325
Amps
23Volts
GTAW-DC
40%
60%
100%