Service access specifications, Environmental specifications – Avaya Sun Fire V880 User Manual
Page 21

Preparing for installation
Issue 2.0 June 2004
21
Service access specifications
Environmental specifications
For the most reliable system operation:
●
The room must have sufficient air conditioning capacity to support the cooling needs of
the entire system.
●
The air conditioning system must have controls that prevent excessive temperature
changes.
●
Do not turn on the computer until it has acclimated to the room temperature for at
least 24 hours.
Follow the guidelines in the table below for temperature, humidity, and altitude limits for
units in operation and for units that are not in operation (that is, units that are in transit or in
storage).
Parameter
English value
Metric value
Front
36 inches
91 centimeters
Rear
36 inches
91 centimeters
Left
36 inches
91 centimeters
Right
36 inches
91 centimeters
Parameter
Operating
(in service)
Nonoperating
(not in service)
Temperature
41°F to 95°F (5°C to 35°C)
IEC 68-2-1, 68-2-2
-4°F to 140°F (-20°C to 60°C)
IEC 68-2-1, 68-2-2
Humidity
(max)
20% to 80% RH
noncondensing; 27°C max wb
IEC 68-2-2, 68-2-3
93% RH
noncondensing at 40°C
IEC 68-2-2, 68-2-3
Altitude (max)
10,000 feet (3 kilometers)
IEC 68-2-40, 68-2-41
40,000 feet (12 kilometers)
IEC 68-2-40, 68-2-41