4.0 Principle of Operation

The ATRT-01 measures transformer turns ratio by applying a test voltage across the (H) winding
and sensing induced voltage on the secondary (X) winding. (For safety, testing is always done in a
step-down transfer, regardless of the transformer’s actual use.) There's no load on windings during
testing, so measured voltage ratio is virtually the same as the winding turns ratio. The ATRT-01
measures turns ratios in a range from 0.8 to 15,000. Excitation current (via H leads) is measured
for reference and ranges from 0.0 to 2,000 mA (0 to 200 milliamperes for ATRT-01B and ATRT-
01D). Winding polarity is displayed as "

+

" (in phase) or "

-

" (out of phase). The ATRT-01

calibrates its own sensing circuits before each test; therefore, calibration by the operator is not
required.

5.0 Specifications

Model ATRT-01(v) specifications are listed below in Table 5-1

Table 5-1. Model ATRT-01 (v) Turns-Ratio Meter Specifications

(Unless otherwise indicated, each specification is the same for all three ATRT-01 models.)

Type

Portable, Automatic, Single-Phase Transformer Turns-Ratio Meter

Size (inches)

12 L by 8 W by 9 H

Weight (pounds)

ATRT-01: 8, ATRT-01B: 9.5, ATRT-01D: 9.5

Turns Ratio-Measuring Ranges

0.800 to 15,000.00

Turns-Ratio Accuracy

0.8-999:

?

0.1 %

1,000-1,499:

?

0.2 %

1,500-1,999:

?

1.0 %

2,000-15,000:

?

2.0%

Calibration

Self Calibrating; No operator calibration required

Excitation Voltage

ATRT-01: 40 Volts ac, ATRT-01B/ATRT-01D: 20 Volts ac

Excitation Current

ATRT-01: 2 amps, ATRT-01B/ATRT-01D: 0 to 200 milliamperes

Current Accuracy

?

2 % of Reading (

?

1 Digit)

Winding Polarity

Displayed on LCD screen

Display

LCD: 20 Characters wide by 4 Lines, viewable in bright sunlight

Serial Interface

RS-232C, 19200 baud, 8 data bits, 2 start bits, 1 stop bit

Temperature

?

Operating: -20

?

C to 55

?

C

?

Storage: -40

?

C to 65

?

C

Warranty

One-Year on Parts and Labor