Nbox/einc installation instructions - sheet 2, Check current loop network, 4 installation - configuration – TREND NBOX_EINC User Manual
Page 6: Connect to einc with ip tool, Configure addressing details with iptool
2 - 2
NBOX/EINC Installation Instructions TG200152 Issue 2/D 4/7/06
NBOX/EINC
Installation Instructions - Sheet 2
9 10
~
230V
RDS/RS232
!
24V
~
MODEM
EINC
O
I
NBOX/EINC
?
NBOX/EINC
?
( T - )
( T + )
( R - )
( R + )
( T - )
( T + )
( R - )
( R + )
9 10
13
Check Current Loop Network
b
TX
a
RX
c
OK
IQ Faulty
Check network cabling for
short circuits with a
multimeter (NOT Megger)
Network Address Invalid
OK
OK
NBOX/EINC
Power up other nodes until
faulty node is found
(OK
). Correct fault.
(yellow)
(yellow)
(green)
0,2,3 or >119
Check baud rate
1.4 INSTALLATION - CONFIGURATION
(Continued)
14
Connect to EINC with IP Tool
SET Manual TE200147
IP Tool Manual TE200638
Router
EINC
Router
Either over Ethernet
or Local PC Ethernet Connection
SET v6
(including IP Tool)
XCITE/XA crossover adaptor
order separately (XCITE/XA/5
pack of 5)
SET v6
(including IP Tool)
Local PC (Ethernet) connection can be either to adjacent Ethernet
hub using standard cable only, or directly to EINC using standard
cable and crossover adaptor, XCITE/XA.
Initially access EINC via its MAC address
15
Configure Addressing Details with IPTool
EINC Data Sheet TA200137
IP Tool Manual TE200638
Parameter
Setting
Default
Function
Condition
Note
Address Module
IP Address
IP address
0.0.0.0 to 255.255.255.255
128.1.1.
Ethernet IP address
Last section set automatically
to address switch setting
1
Subnet Mask
Mask
0.0.0.0 to 255.255.255.255
255.255.
255.0
Mask applied to IP address to generate
subnet number
All EINCs on same channel
must be on same subnet to
create internetwork
1
UDP Port
0 to 65535
57612
Ethernet UDP port used by IQ system
equipment on Ethernet
All IQ system devices must
use same port to
intercommunicate
2
Router 1
IP address
0.0.0.0 to 255.255.255.255
0.0.0.0
IP address of router on same subnet as
EINC
MUST be set up for
communications outside own
subnet
3
Lan number
Lan number 1, 4 to 9, 11 to 119 20
Lan number of EINC on internetwork
4
Identifier
15 alphanumeric characters -
not /\({;?* characters
EINC
Identifier for EINC
Always set up for
supervisors/display panels