King Electric GPT 3 User Manual
Page 9

Page 9 of 21
Specifi cations
Control
Range:
41° to 77°F (5° to 25°C)
Dead band:
2°F (1°C)
Electrical
Supply:
120, 208, 240 or 277 volts auto-selected
Heater load:
30 amps maximum
Alarm relay:
Isolated SPDT 1 amp Class 2 contact
Indicators
Supply (red)
Power applied
Heater (yellow)
Call for heat
GFEP (red)
Ground fault occurring or has occurred
FAULT (red)
Contactor failure
Temperature sensor failure
Power-on
self-check
failure
GFEP
Settings:
30 mA default, 60, 90, 120 mA selectable
Reset:
Manual default, automatic selectable
Auto-test:
Every 24 hours
Heater monitoring
Choices:
Self-limiting default, constant wattage selectable
Alarm relay:
No power
Heater
failure
Contactor
failure
Ground fault or GFEP circuit failure
Temperature sensor failure
Temperature limits
Operating: −40° to 136° F (−40° to 58° C)
Storage:
−
67° to 167° F (−55° to 75° C)