Generator performance, Prepare the generator for operation – Gillette Generators SPP-180 User Manual
Page 15

PAGE 15
A flexible LPG fuel line is furnished for
installation between the LPG fuel line & generator fuel 
input. 
 
CAUTION: Make sure this flexible fuel line is 
installed in a horizontal position, without bends. 
A bend of any kind, in this flexible line could lead 
to an eventual crack in the bend, causing a 
possible fuel leak. See Figure 6 for recommended 
installation. 
 
Make sure fuel line installation includes an on/off
manual gas valve at both the LPG tank and at 
connection point of generator. 
 
All new installations, plus any future repair or
troubleshooting procedures must include an LPG 
manometer test. This test should be conducted after 
all other LPG appliances are turned on. After all 
appliances are working, start the generator. If 
manometer stays within 10 to 12 inches water column 
with full load applied to generator, it’s a good 
installation. (See Figure 6) If manometer reading 
falls below 10 inches water column while generator is 
cranking or running, it may indicate the primary 
regulator on LPG tank is wrong or the LPG tank is too 
low to produce the vapors required to operate 
generator. 
 
If manometer reading stays within 10 to 12 inches 
water column, but generator will not run properly, it 
may indicate fuel line length is too long or fuel line 
diameter is too small to deliver proper volume of fuel. 
Check calculations from charts in Figure 4 and 5. 
 
Figure 6 
NOTE: After completion of all gas tests, remove 
manometer and replace blank plug, using fresh pipe 
sealant. 
Climates that have snow and ice build-up, along
with sub-zero temperatures should have LPG fuel 
pipe protection against freezing. The generator end 
of the hard piping installation should include a 
sediment trap to drain any condensation and a line 
filter. (See Figure 6) 
Best installations happen when electric utility
meter and LPG tank are reasonably close (20 Ft. to 50 
Ft.), as it results in short runs for both electric wires 
and LPG fuel lines. When these two identities are far 
apart, always choose to locate generator as close to 
the LPG tank as possible, because installation costs 
are lower when increased wire size must be used for 
longer runs rather than increased fuel pipe dia. 
GENERATOR PERFORMANCE
When matching a generator to a specific application, 
whether gross intermitted or gross continuous power 
is used, it is important to derate this power output for 
the following adverse conditions: 
Engine power rating after “break-in” is usually
within 3% of engine published rating.
Temperature
and
altitude
directly
derate
generator power. Derate 3½% for each 1,000 feet 
above 326 feet, over sea level. Derate 1% for every 
10º F (5.6º C) over 77º F (25º C). 
Generator location is important. If it is located
too far from fuel source, fuel line may not deliver 
adequate fuel. If it is located too far from electric 
distribution box, the electric power lines may not 
deliver adequate electric power. Both examples will 
directly
affect
generator power.
Read
section
“The
Gaseous
Fuel
System
Installation”
on
page 12 & 14 for 
full details. 
All 
generator
access doors are 
locked, 
and
are
opened with a common key for
all locks. Notice the door lock (in the locked position) 
has matching dot system in alignment. Insert the key 
into lock and turn counterclockwise. Remove the key 
and note, the dots are now out of alignment. Re-insert 
PREPARE THE GENERATOR
FOR OPERATION
Stationary Dot
Dot-aligned, 
Locked 
Position 
Un-Locked 
Position 
Raised 
Finger 
Hold 
ACCESS TO HOUSING INTERIOR
Sediment Trap
Dedicated LPG
Fuel Line from
LPG Tank
Manometer
Reading
Must Be 6”
to 7” Water
Column
Gas Fuel To
Generator
On/Off Valve
Furnished
Flexible
Gas Pipe
(without
bends or
angles)
Manometer Port: Remove
Blank Plug And Insert
Manometer Plug
Line Filter
