FIG 2: CHART TO DETERMINE SIZE OF BATTERY PACK

MIN

1 HR

2 HR

4 HR

8 HR

16 HR

24 HR

48 HR

72 HR

UL STD.

150 MA

300 MA

500 MA

1 A

2 A

3 A

4 A

5 A

7.5 A

10 A

4 AH

4 AH

4 AH

4 AH

4 AH

4 AH

4 AH

4 AH

4 AH

4 AH

4 AH

4 AH

4 AH

4 AH

4 AH

4 AH

4 AH

4 AH

4 AH

4 AH

4 AH

4 AH

4 AH

4 AH

4 AH

4 AH

4 AH

4 AH

8 AH

8 AH

8 AH

8 AH

8 AH

8 AH

12 AH

16 AH

20 AH

12 AH

12 AH

16 AH

16 AH

20 AH

16 AH

20 AH

12 AH

20 AH

12 AH

20 AH

12 AH

20 AH

8 AH

8 AH

12 AH

12 AH

16 AH

16 AH

24 AH

36 AH

24 AH

24 AH

36 AH

28 AH

28 AH

24 AH

36 AH

48 AH

36 AH

44 AH

72 AH

100AH

24 AH

32 AH

40 AH

60 AH

72 AH

52 AH

72 AH

84 AH

130AH

180AH

48 AH

72 AH

100AH

120AH

180AH

240AH

48 AH

100AH

150AH

200AH

240AH

360AH

480AH

72 AH

150AH

240AH

300AH

360AH

480AH

720AH

BACKUP TIME DESIRED

T

O

TA

L CU

RR

E

N

T

D

R

A

W

N

"MIN" TIME REFERS TO FACILITY USING A GENERATOR WHERE THE BATTERIES

ARE ONLY REQUIRED TO OPERATE THE SYSTEM FOR A FEW MINUTES

U.L. STANDARD REQUIRES 4 HOURS OF BATTERY OPERATION FOLLOWED BY

A 24 HOUR RECHARGE PERIOD AND THEN A SECOND 4 HOURS OF OPERATION

STANDARD SECURITRON POWER SUPPLIES CAN ONLY CHARGE UP TO A 20AH PACK.

MODIFIED EQUIPMENT. LARGER PACKS ARE SHOWN IN ITALICS IN THE CHART.

IF A LARGER PACK IS CALLED FOR, THE FACTORY MUST BE ALLERTED TO SUPPLY

BATTERIES MUST BE SEALED LEAD ACID OR GEL CELL TYPES.

DRY CELLS WILL NOT RECHARGE AND WILL BE DAMAGED.

THIS CHART IS ONLY VALID IF BATTERIES ARE OPERATED

AT ROOM TEMPERATURE. IN A COLD ENVIRONMENT, CAPACITY IS REDUCED.

BATTERIES SHOULD BE REPLACED AFTER 5 YEARS OF USE.


3.8 CODE APPROVED WIRING METHODS
Note that these units are Class 2 rated. This means that the individual DC outputs of the

supplies (on “P” terminals) are current limited and can pose neither a high voltage nor high
energy hazard outside of the enclosure. Electrical building codes in most jurisdictions permit
Class 2 wiring to be done “in the open” rather than in conduit. To maintain the Class 2
ratings
on the “P” terminal outputs, never connect them together to obtain higher capacity.
If you require higher capacity use the “H” terminal but the “H” terminal is high current (not Class

2) and must be in conduit. The line voltage wiring coming into the unit also must be in conduit
as it poses a high voltage hazard. Be sure to check with your local building department to
make sure you are complying with applicable wiring codes before installing these units.

4. SLAVE BOARD
Your power supply may include more than one control board. If so, the other board will be a

"slave" board (part # CCB-8) whose only purpose is to provide eight additional "P”, and "R"
terminals. The board will not be fully populated as the functions of AC input, battery charging,
emergency release, voltage supervision and DC and AC fusing are only needed on the CCS8M
board. The eight additional Class 2 “P” terminals naturally constitute individual outputs
protected by Polyswitches and including zone LED’s and slide switches.


5. APPROVALS
All Securitron power supplies are tested by various agencies. Consult the label inside the supply
to be advised of current approval status