Securitron PS-1M_Series User Manual
Page 3

PN# 500-20400
Page 3
Rev. D, 08/11
FIG. 2: WIRING
AC
F
AC
RED
BLACK
VOLTAGE
ADJUST
LOW VOLTAGE
AC FROM
TRANSFORMER
UNCONNECTED
TERMINAL FOR
SWITCH HOOKUP
OUTPUT
DC
DC
BATTERY
PACK
2.5 AMP
POLYSWITCH
BREAKER
3.5 EMERGENCY RELEASE
Emergency release of DC output at the board is most easily
accomplished by using the unconnected "F" terminal.
Connect the NC contacts of the release switch between "+"
and "F" and then connect the load to "-" and "F". When the
emergency release contacts open, all DC power will be cut
off. When the connection is to a UL listed fire alarm
system, use auxiliary latching normally closed contacts
with contact ratings of at least 2 Amps. Do not use
"trouble" contacts. Note the drawing to the right.
4. MAGNACARE
LIFETIME REPLACEMENT WARRANTY
For warranty information visit: www.securitron.com/en/site/securitron/About/MagnaCare-Warranty/
F
NORMALLY
CLOSED
SWITCH
CONNECT "+" DC
LOAD TO "F"
TERMINAL WHEN
ADDING SWITCH
FOR EMERGENCY
RELEASE