FIG. 2: WIRING

AC

F

AC

RED

BLACK

VOLTAGE
ADJUST

LOW VOLTAGE
AC FROM
TRANSFORMER

UNCONNECTED
TERMINAL FOR
SWITCH HOOKUP

OUTPUT

DC

DC

BATTERY
PACK

2.5 AMP
POLYSWITCH
BREAKER

3.5 EMERGENCY RELEASE
Emergency release of DC output at the board is most easily
accomplished by using the unconnected "F" terminal.

Connect the NC contacts of the release switch between "+"

and "F" and then connect the load to "-" and "F". When the
emergency release contacts open, all DC power will be cut
off. When the connection is to a UL listed fire alarm
system, use auxiliary latching normally closed contacts
with contact ratings of at least 2 Amps.
Do not use
"trouble" contacts. Note the drawing to the right.