Cl-l, Ch-p cpl 8.30 full, 11 english – Robinair 17801B Recovery, Recycling, Recharging Unit User Manual
Page 13: Operating instructions
Model 17800B / 17801B Recovery/Recycling/Recharging Unit
11
ENGLISH
The.“CL-L”.message.shows.on.the.display.if.there.is.pressure.in.the.unit,.and.a.
self-clearing.process.of.the.components.begins..You.can.press.
HOLD/CONT.to.
bypass.clearing.if.an.accurate.recovery.amount.is.not.required..Otherwise,.the.
compressor.will.start.and.the.“CL-L”.message.remains.on.the.display..This.process.
takes.from.20.seconds.to.four.minutes.to.complete..Once.the.clearing.is.complete,.
the.unit.automatically.begins.to.recover.refrigerant.from.the.system..If.there.is.no.
internal.pressure.in.the.unit,.refrigerant.recovery.begins.immediately.
CAUTION:
If the A/C system pressure is 25 psi or less, the
message “CH-P” appears on the display to alert you not to attempt
recovery from an empty system. Do not press HOLD/CONT to
continue the recovery process unless you know the A/C system
contains refrigerant.
The.display.shows.that.the.unit.is.in.the.RECOVER.mode.and.the.AUTOMATIC.
cycle..You.can.monitor.the.amount.of.refrigerant.removed.from.the.system.by.
watching.the.display..The.compressor.shuts.off.automatically.when.recovery.is.
complete.(at.approximately.13.inches.of.vacuum)..The.display.shows.the.“CPL”.
message,.and.then.alternately.flashes.the.weight.of.refrigerant.recovered.
. 5.. To.assure.complete.recovery.of.refrigerant,.wait.for.five.(5).minutes.and.
watch.the.manifold.gauges.for.a.rise.in.pressure.above.“0.”.If.a.rise.occurs,.
press.
HOLD/CONT..Repeat.as.needed.until.the.system.pressure.holds.for.
two.(2).minutes.
CAUTION:
Drain the oil from the separator only after each
recovery.
Do not completely depressurize the oil separator; immediately close
the valve when oil is completely drained in the next step. The lower
right corner of the display will indicate “OIL (OUNCES)” as a reminder.
. 6.. Verify.the.oil.catch.bottle.is.empty,.then.slowly open.the.oil.drain.valve,.
and.drain.the.oil.into.the.oil.catch.bottle..This.oil.was.removed.from.the.
A/C.system.during.recovery..It.must.be.replaced.with.new.oil..When.all.the.
recovered.oil.has.completely.drained,.immediately.close.the.valve.and.record.
the.amount.of.oil.in.the.bottle..Dispose.of.waste.oil.in.an.appropriate.manner.
If the recovery tank fills completely:
• The compressor shuts off; the digital display shows the message “FULL.”
• Change the tank.
The.A/C.system.is.now.empty..Make.any.repairs.at.this.time.
Weight Example
Operating Instructions
HOLD
OIL(OUNCES)
HOLD
LBS
RECOVER
Hold
HOLD
LBS
RECOVER
CL-L
HOLD
CH-P
CPL
8.30
FULL
FLASHES