FIRE ALARM CONTROL PANEL

MADE IN AMERICA

FORM# 350305 Rev. C 12/06

Copyright © 2006 Silent Knight

This document is not intended to be used for installation purposes. We try to
keep our product information up-to-date and accurate. We cannot cover all
specific applications or anticipate all requirements. All specifications are
subject to change without notice. For more information, contact Silent Knight
7550 Meridian Circle Suite 100, Maple Grove, Mn 55369-4927.
Phone: (800) 328-0103, Fax: (763) 493-6475.

SK-4 & SK-4E

Fire Control Panel
Engineering Specifications

Electrical Specifications (cont)
Auxiliary Output

Resettable and non-resettable
Operating Voltage: 24 VDC nominal
Current: 500 mA max, power-limited;
total current for nonresettable power,
resettable power and two NACs must
not exceed 6.0A (requires additional
transformer)

Battery

Type: Sealed lead acid only
Charging Circuit: 27.6 VDC @ 0.8A
max normal flat charge
Charging Capacity: 18 AH
Size: 7 AH max allowed in FACP.
Larger batteries can housed
in an RBB accessory cabinet

Compatible Initiating and NAC
Devices
See SK document PN 52612.

Mechanical Specifications
Cabinet Backbox Dimensions:
14.5" W x 15" H x 3" D
(36.83 W x 38.10 H x 7.62 D cm)

Cabinet Door:
14.677" W x 15.342" H x 0.375" D
(37.28 W x 38.97 H x 0.95 D cm)

Cabinet Color: Red

Telephone Requirements:
FCC Part 15 and Part 68 approved
Type of Jack: RJ31X (two required)

Installation
The SK-4/E can be surface mounted
using two key slots at the top of the
backbox and two additional 0.25”
diameter holes at the bottom, or semi-
flush mounted using the optional Trim
Ring P/N TR-1-R

Approvals
NFPA 72; UL Listed;
CSFM 7165-0559: 145;
MEA 297-01-E-3

Ordering Information

SK-4
120 VAC Four Zone Conventional
FACP

SK-4E
240 VAC Four Zone Conventional
FACP

Accessories

SK-DP2/4
Dress Panel. Allows access to the
panel controls but restricts access to
system wiring.

SK-CAC4
Class A Convertor. Converts Style B
(Class B) IDCs to Style D (Class A) and
Style B (Class B) NACs to Style Z
(Class A)

SK-4XTM
Transmitter Module. Provides a
supervised output for local energy
municipal box transmitter and alarm
and trouble reverse polarity.

SK-4XLM
LED Interface Module.

SK-XRM24
110 Volt Transformer 3–6A.

SK-XRM24E
220 Volt Transformer 3–6A.

SK-RZA4
Remote Annunciator.

SK-4XZM
Zone Relay Module.

RBB
Remote Battery Box Accessory
Cabinet. Use if back up batteries are
too large to fit into FACP cabinet.
Dimensions: 16”W x 10”H x 6”D

Digital Communicator Accessories

5104B
Six-zone fire control communicator

5129
Four channel slave fire communicator

The contractor shall provide a completely electrically supervised fire alarm control panel Silent Knight Model SK-4/E. The system shall contain a fire

alarm control panel capable of operating and supervising smoke detection devices, alarm notification devices, and an on-board annunciator. It shall be

compatible with a digital communicator accessory.
The fire alarm control panel shall have a power limited supply, four Class B initiation circuits which shall accommodate heat detectors, smoke detectors,

and manual pull stations. Smoke detection shall be achieved with either 2- or 4-wire detectors that are compatible with the system. The initiation inputs

shall be programmable as 1) verification zones in which detectors are automatically reset one time before signaling an alarm condition; or 2)

combination waterflow supervisory zones that allows the FACP to distinguish between an alarm switch (waterflow device) and a supervisory switch

(tamper) installed on the same circuit. The FACP shall have two 2.5 amp or 5 amp (with an additional optional standard transformer) programmable

notification outputs. It shall have dedicated relays for alarm, trouble, and supervisory. It shall have two power outputs, one resettable and one non-

resettable, each rated at 500 mA.
The FACP shall have an on-board annunciator to indicate alarm, supervisory, trouble, and maintenance conditions. The annunciator must include LEDs

for AC, GENERAL TROUBLE, ALARM SILENCE, WALK TEST, EARTH FAULT, AND LOW BATTERY. The annunciator shall also contain LEDs to

annunciate fire alarms, troubles, supervisory, and maintenance by zone. The FACP must be fully operational from the annunciator and include buttons

for ACKNOWLEDGE, ALARM, SILENCE, RESET, and WALK TEST. The annunciator must also have separate DISABLE switches for each zone and

notification circuit.rr