Ga ex ia iic t4, Cenelec / iec, Is system drawing – Fire Fighting Enterprises Talentum IR3 Flame Detector User Manual

Page 4

background image

4

CENELEC / IEC





Ga Ex ia IIC T4





















Table 2 Type of Protection Codes

Table 3 Temperature Classification



Table 4 Subdivisions of Group II Gases

Temperature

Class

Referred to

ambient of

-20°C to +40°C

Maximum

Surface

Temperature

T6 85°C

T5 100°C

T4 135°C

T3 200°C

T2 300°C

T1 450°C

Detectors approved to T4 at 40°C

Code

Type of
Protection Code

Equipment

Category

ia Intrinsic

safety

1

ib Intrinsic

safety

2

d

Flameproof 2

These Flame Detectors are approved ia.

Gas Group

Representative Gas

Other Gases, Liquids, Vapours

IIC

Hydrogen

Acetylene, Carbon Disulphide

IIB

Ethylene

Diethyl ether, Tetrafluoroethylene

IIA

Methane

Butane, Methanol, Petroleum, Propane, Styrene

These Flame Detectors are approved IIC for listed gases in EN 60079-0.

Equipment
Protection
Level (EPL)

[See EN60079-26]

Explosion Protection
symbol

13

IS System Drawing























































Hazardous Area

2

1

-

+

Flame Detector

Safe Area

i

+

-

-

24V DC Normal

(Break supply to reset

if detector set to latch)

i

= See detector data

sheet for details

-

+

24V DC Normal

(Break supply to reset

if detector set to latch)

Zone

Fault
Relay

Fire
Relay

2

1

-

+

Flame Detector

6

5

7
8

Fault
Relay

Fire
Relay

2

1

-

+

Flame Detector

6

5

7
8

EO

L

Refer to note 6

Barrier

(2 channel)

+

-

-

+

NOTE 1
Each Barrier fed circuit must be a separate circuit and
must not be connected with any other electrical circuit.

NOTE 2
The electrical circuit in the hazardous area must be
capable of withstanding a test voltage of 500 VAC to
earth for 1 minute.

NOTE 3
The installation must comply with EN 60079-14:2003


Barrier

+

-

+

NOTE 5
The cable may be separate cables or a twin pair
contained in a type ‘A’ or a type ‘B’ multicore cable (as
defined in clause 8 of EN60079-25).

Baseefa Certificate Related Drawing

No modifications permitted without the

approval of the Technical Director

Safe Area Apparatus


The barriers and isolators are to be
supplied from apparatus which is
unspecified except that it must not
be supplied from nor contain in
normal or abnormal conditions a
source of potential with respect to
earth in excess of 253 volts r.m.s. or
253 volts d.c.

NOTE 6
If required a loading resistor having a surface area
greater than 20mm² may be connected in the fault relay
circuit circuits.

Detector Input Parameters

Terminal 1 with respect to terminal 2

Terminal 3 with respect to terminal 4

Ui = 30V

Ii = 100mA

Pi = 0.65W

Ci = 0.03µF

Li = 0

Terminal 5 with respect to terminal 6
Terminal 7 with respect to terminal 8

Ui = 30V

Ii = 100mA

Talentum Developments Ltd
www.Talentum.co.uk

Title: - 016XXX Series I.S. System Drawing

Rev: A Drawn by: J.A.B. Checked by: J.P 17/04/08

Drawing number: A4/1468/07 Sheet 1 of 2