TESTING THE SYSTEM
Following installation, test the system as follows :-
First ensure that the system is running and has been allowed time to calibrate (50 seconds after power-
up or reset).
Fire Alarm
Place the striped end of the test filter over the Receiver lens.
A Fire Alarm shall be indicated in approx 10 to 12 seconds.
Fault Alarm
Place a complete blockage (example: a hand) over the Receiver lens. Ensure that the lens is
fully covered.
A Fault Alarm shall be indicated in approx 4 to 6 seconds.