FEC DSP1500 (SAN3) User Manual
Page 19

enFORCE
Operation Manual
PAGE 4 - 19
Chapter 4: System Setup and Wiring
4.8.2 Special Configuration Settings (DIP Switch 1~3)
1 ON:
CAL/Zero acceptance window = +/-10% of full scale load.
OFF: CAL/Zero acceptance window = +/-4% of full scale load. (Default)
2 ON:
Parameter changes made by communicating are not saved on EEPROM.
OFF:
Parameter changes made by communicating are saved on EEPROM. (Default)
3 ON: Ramp Up / Down Disabled
The speeding up and slowing down is done rapidly.
It is used to gain cycle time, etc., however, the burden on the gear will be greater.
OFF: Ramp Up / Down Enabled
(Default)
The speeding up and slowing down is done slowly.
The diagrams below show the effects of the DIP switch 3 setting as seen on an
oscilloscope for a DPT-021R1 press (top 2 diagrams) and a DPT-201R3 press (bottom 2
diagrams). Both presses were set up to run Distance Control at maximum speed with the
brake disabled (always disengaged).
If not used, set DIP switches number 1 thru 3 in the OFF position.
SAN Unit must be powered off and on again for switch changes to take effect.
Advance
Return
470ms
30ms
470ms
470ms
Advance
Return
190ms
30ms
190ms
85ms
Advance
Return
488ms
14ms
488ms
456ms
Advance
Return
96ms
14ms
96ms
90ms
DIP Switch 3 OFF
DIP Switch 3 ON
DIP Switch 3 OFF
DIP Switch 3 ON
DPT-021R1
DPT-201R3