Table 8 Approximate Back-up Times

Load(VA)

100Ah 24VDC(min)

200AH 24VDC(min)

300 457.5

972.2

600 208.1

499.5

900 140.6

262.3

1200 103

178.1

1500 77.8

138.3

1800 57.6

113.2

2100 49.5

100.5

2400 41.4

87.9

2700 33.2

75.3

3000 28.4

62.6

Note: Back-up times depend on the quality of the battery, age of battery and type of battery.

Specifications of batteries vary from one manufacturer to another.

Table 9 General Specifications

Safety Standard

EN60950-1:2006+A1: 2010
EN62040-1-1: 2008

EMC Standard

EN62040-2 : 2006 C2

Operating
Temperature Range

0°C to 45°C

Storage temperature

-15°C~ 60°C

Altitude, operational

Elevation: 0 – 1500 Meters

Relative humidity

5% to 95% non-condensing

Audible Noise

60dB max

Cooling

Forced air

Dimension(L*W*H)

330mm*268mm*76mm

Net Weight

4.9KG

DC wiring

Double 6 AWG cable for each polarity

AC input/output

L/N/G:12AWG