beautypg.com

Table 6 invert mode specifications – PROLiNK IPS3000 User Manual

Page 15

background image

13

Table 6 Invert Mode Specifications

MODEL IPS3000P

Output Voltage Waveform

Pure Sine Wave

Rated Output Power

3000VA

Power Factor

0.8

Nominal Output voltage

230Vac

Minimum Peak Output Voltage at

Rated Power

>200V

Output Frequency(Hz)

50Hz / 60Hz ± 1Hz (follow first connect to grid)

Output Voltage Regulation

±10% Vrms

Nominal Efficiency

>90% (@Normal DC Input; >60% R load)

Over-Load Protection

fault after 5s@≥150% load,<=200% load

fault after 10s@110%~150% load,

Surge rating

6000VA

Capable of starting electric motor

1.5HP

Output Short Circuit Protection

Current limit (Fault after 4 cycles max)

Nominal DC Input Voltage

24V

Min DC start voltage

20V

Low DC Alarm

21.0 ± 0.6Vdc

Low DC Alarm Recovery

21.6 ± 0.6Vdc

Low DC Shut-down

20.0 ± 0.6Vdc

Low DC Shut-down Recovery

22.0 ± 0.6Vdc

High DC Shut-down

30.0 ± 0.6Vdc

High DC Shut-down Recovery

29.0 ± 0.6Vdc

DC component of output

<100mV

Power Limitation