Sprinkler option temperature controller settings – American Dryer Corp. ML-310 User Manual

Page 79

background image

75

Sprinkler Option Temperature Controller Settings

NOTE: Refer to Controller’s User’s Manual for further information on controller options.

Message

Display

Message

Description

Settings

SECr

SECURITY CODE

FULL SECURITY -

SET TO 110 (DISPLAYED AS 1) "VIEW ONLY"

NO SECURITY -

SET TO 111 (DISPLAYED AS 4)

"ALL FEATURES UNLOCKED"

InP

INPUT DEVICE

P 385 = RTD

INPUT

F-C

º F OR º C

SELECT TYPE REQUIRED

(FAHRENHEIT OR CELSIUS)

dPt

DECIMAL POINT

0, NO DECIMAL POINT

InPt

INPUT FAULT TIMER

0.2

SPL

SET POINT LOW

500

(SETTING CANNOT BE LOWER)

SPH

SET POINT HIGH

700

(SETTING CANNOT BE HIGHER)

SPSt

SET POINT STATE

rE

(REVERSE ACTION)

SPLP

SET POINT LAMP

0

o

FF

(LAMP OFF WHEN OUTPUT IS ON)

AL

HIGH ALARM ONLY

Hi

ALt

ALARM TYPE

Abs

(ABSOLUTE ALARM)

ALrE

ALARM RESET

OnOF

(AUTOMATIC RESET)

ALPi

ALARM POWER

INTERRUPT

OFF

(ALARM INHIBIT IS OFF)

ALiH

ALARM INHIBIT

OFF

(ALARM INHIBIT IS OFF)

ALSt

ALARM OUTPUT

STATE

CLOS

(CLOSES CONTACTS AT ALARM SET POINT)

ALLP

ALARM LAMP

0 ON

(ALARM LAMP IS ON WHEN ALARM CONTACT IS CLOSED)

ALHi

ALARM HI

575º F OR 301.6º C

(NOTE: ADJUST SAME AS SP)

Cy

CYCLE RATE

OnO F

SP_d

SET POINT ON-OFF

DIFFERENTIAL

-1

rt

RAMP TIME

OFF

InPC

INPUT CORRECTION

0

FiLt

DIGITAL FILTER

2

SP

TEMPERATURE

SET POINT

575º F OR 301.6º C

Note: When message display (Cy) set to OnOF.
SPOL (SET POINT OUTPUT LOW LIMIT) not in use.
SPOH (SET POINT OUTPUT HIGH LIMIT) not in use.
Are not displayed.