310 (gas) non-tilt, 15 hp blower/5 hp drive motor, Electrical service specifications (per dryer) – American Dryer Corp. ML-310 User Manual
Page 30

26
2. Electrical Service Specifications
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is
affixed to the right electrical control panel.
WARNING: 208 VAC and 230 VAC ARE NOT THE SAME. Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
NOTE: ADC reserves the right to make any changes in specifications at any time without notice or
obligation.
310 (Gas) Non-Tilt
15 HP Blower/5 HP Drive Motor
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT: 208 VAC and 230 VAC ARE NOT THE SAME. When ordering, specify
exact voltage.
NOTES:
A. Fuse ratings are dual element, time delay, current limiting, class RK1 or RK5 ONLY.
B.
Circuit breakers are thermal/magnetic (industrial) motor curve type ONLY. For others,
calculate/ verify correct breaker size according to appliance amp draw rating and type of
breaker used.
C. Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
FUSING
CIRCUIT
BREAKER
Dual Element
Time Delay
208
3ш
3/4
57
80
90
230
3ш
3
53
80
90
380
3ш
3/4
31
50
60
416
3ш
3/4
29
50
60
460/480
3ш
3/4
30
50
60