1.6.4.4 Measurement Type: Level & Interface
Display
Action
Comment
1
Status
Level
% Output
Loop
Transmitter Display
Transmitter default display. Status, Level, % Output, and Loop
values cycle every 8 seconds.
2
Level
xxx.xx
Transmitter Display
Level measurement in centimeters or inches
3
% Output
xx.xx%
Transmitter Display
Level as a percentage of loop current span
4
Loop
xx.xx mA
Transmitter Display
Loop current output (mA)
5
IfcLevel
Transmitter Display
Displays interface level
6
MeasType
Select type of measurement
Choose Lvl&Ifc
7
Units
Select units of length
Choose cm or in
8
Probe Ln
xxx.x
Enter exact length of probe
6–420 inches (15.24–1066.8 cm)
9
Set 4mA
xxx.xxlu
Enter the PV value for 4 mA
point
Enter 4 mA point in level units
10
Set 20mA
xxx.xxlu
Enter the PV value for 20 mA
point
Enter 20 mA point in level units
11
Lvl Ofst
xxx.xxlu
Enter the level offset value
Changes zero level as referenced from probe tip
12
Damping
xx.x s
Enter damping filter time
0–1 second in 0.1 increments
1–25 seconds in 1.0 increments
13
Fault
22mA
Select loop current under
fault condition
3.6 mA, 22 mA or Hold
14
Poll Adr
xx
Enter HART polling address
number
0–15
15
Trim 4
xxxx
Adjust 4 mA point
Attach a meter to the output. If the output does not equal 4 mA,
adjust the value of the display until the meter reads 4 mA
16
Trim 20
xxxx
Adjust 20 mA point
Attach a meter to the output. If the output does not equal 20 mA,
adjust the value of the display until the meter reads 20 mA
17
Loop Tst
Enter a mA value
Set mA output to a value between 3.6 and 22.0 mA
18
DeadBand
xx.x
Factory Setting
Diagnostic, factory setting
19
Snsr Mnt
Enter mounting type
MLI Top (external probe; transmitter top mounted)
MLI Bot (external probe; transmitter bottom mounted)
Dir Near (NPT, BSP, and 600# or less flanged probe)
Dir Ext (flanged probes 900# class and over)
20
Trim Lvl
xx.xx
Enter value to adjust Level
reading
-20.00 inches
≤ Trim Lvl ≤ 20.00 inches
21
Trim Ifc
xx.xx
Enter value to adjust Interface
reading
-20.00 inches
≤ Trim Ifc ≤ 20.00 inches
22
F1 Cnts
Display only
For factory diagnostic use
23
F2 Cnts
Display only
For factory diagnostic use