HERYTAGE SPECIFICATIONS

MODEL

2kVA

1.6kW

3kVA

2.4kW

4kVA

3.2kW

6kVA

4.8kW

8kVA

6.4kW

10kVA

8kW

16kVA

12.8kW

20kVA

16kW

AC INPUT

Input ACV & circuit breaker

requirements - standard hardware

connection

120VAC
208VAC
240VAC

20A
15A
15A

30A
20A
15A

50A
30A
30A

60A
50A
40A

-

60A
50A

-

70A
60A

-

100A

90A

-

125A
110A

Line Cord

1

(optional)

120VAC
208VAC
240VAC

C, I, J, E

O, K, L
O, K, L

J, E

K, L

O, K, L

E

L, M
L, M

-

N, P
N, P

-
-
-

-
-
-

-
-
-

-
-
-

Input Voltage Window

+15%, -20% of nominal VAC Input @ full load

+15%, -40% of nominal VAC Input @ 50% load

Frequency

60Hz., ± 3Hz. Adjustable window

AC OUTPUT

Output ACV – Hardwire

120 / 208 / 240

Output Receptacles

Optional

Output waveform

Computer grade sine wave output power with less than 5% total harmonic distortion @ rated kw load.

Regulation

± 3% voltage regulation

Load Compatible

Guaranteed compatible with all loads

Overload

150% surge capability, overload alarm 101% load to 125% load for 10 min. before shutdown.

Greater than 125% the system will shutdown in 5 seconds.

UNIT

UPS Dimensions - H x W x D (in.)

25.5 x 16.2 x 23

2

37.5 x 17.75 x 33.25

39 x 22 x 34

Weight (lbs.)

208

2

275

2

290

2

565

2

465

530

570

665

Effi ciency

87%

88%

90%

91%

93%

93%

91%

91%

Heat Loss BTU/w

816/239

1116/327

1213/355

1619/475

1645/482

2055/602

2160/632

3238/95

Noise Attenuation

120db common mode, 60db transverse (normal) mode

Isolation

Output is completely isolated from commercial power with less than 2 pf effective capacitive

coupling primary to secondary.

Surge Protection

6000 volts are suppressed to safe levels per ANSI/IEEE C62.41 – 1997 category A & B waveforms

Operating Temperature

0º to 40º C (32º to 104º F)

Relative Humidity

0 to 95% without condensation

High altitude operation

Max. altitude 10,000 ft – de-rate 1º C off max operating temp.per 1000 ft. above sea level

Agency

UL 1778, cUL listed

User Interface

Keypad w/ LCD display, RS232 serial communications, dial in modem option

DC & INVERTER

Nominal DC voltage

48VDC

72VDC

96VDC

120VDC

96VDC

120VDC

Charger Amps

8A

Runtime (Standard Battery)

100% Load

50% Load

11 min

32 min

18 min

47 min

11 min

32 min

Overload

150% surge capability, overload alarm 101% load to 110% load for 10 min. before shutdown.

Greater than 110% the system will shutdown in 5 seconds.

Effi ciency (on inverter)

85%

Sound Level (Inverter)

50dBA

50dBA

52dBA

54dBA

55dBA

55dBA

53dBA

55dBA

* Specifi cations may change without notice.

1 Line Cord Designators:

C = 5-20P

I = L5-20P

J = L5-30P

E = 5-50P

O = 6-15P

K = L6-20P

L = L6-30P

M = L14-30P

N = 6-50P

P = L6-50P

2 Weight and Dimensions are for UPS with standard internal runtime