beautypg.com

Options, Technical speci fications – MaxPower Corp GE LP33 Series User Manual

Page 2

background image

Options

> Remote monitoring and diagnostics

via

LAN

or internet

>

UPS

management software facilitates

operation and maintenance of the

UPS

>

SNMP

plug-in card, potential-free

relay contacts

>

RPA

Card: Any single

UPS

can be easily

field-configured for Redundant Parallel
Architecture

(up to 4 units)

>

RS

-232 contact interface, providing

maximum

I

/

O

datapoints

> Dual

AC

input option

> Additional external matching battery

cabinets are available for extended
runtime requirements (Contact the
factory for details)

LP

33-10-UL

MODEL

LP

33-20-UL LP33-30-UL LP33-40-UL LP33-50-UL LP33-60-UL LP33-80-UL LP33-100-UL

Power Rating

Power Factor

Output Capacity

10kVA / 8kW

20kVA / 16kW 30kVA / 24kW 40kVA / 32kW 50kVA / 45kW 60kVA / 54kW 80kVA / 72kW 100kVA / 90kW

Output Power Factor

0.8

0.9

Physical

Weight w/o batteries (lbs)

397

430

772

816

1015

1323

Input

Input Voltage

3 x 208V + N

Output

Output Voltage

120Y / 208 V

Battery

Battery Type

Valve Regulated Lead Acid (VRLA)

General

Audible Noise db(A)

50

55

61

62

65

65

68

Operating Temperature

UPS

: 32° to 104° F (0° - 40° C); Battery: 68° to 77° F (20° - 25° C) recommended

Humidity

0-95%; non-condensing

Safety Classi

fications & Listings

UL

/cUL : UL 1778 / IEC62040 / ISO 9001

EMI C

lassi

fication

FCC P

art 15, Class A, IEC 62040-2 Class A

Surge Protection

IEEE 587

-B / ANSI C62.41-B / IEC 1000-4

Float Voltage

328 VDC @ 68° F (20° C)

Min Discharge Voltage

236 VDC (programmable)

Crest Factor

> 3:1

Voltage Regulation

– Static

+/- 1%

– 100% Step Load

+/- 1%

+/- 2%

Voltage Distortion

– 100% Linear Load

< 2% THD

< 1.5% THD

< 2% THD

– 100% Non-Linear Load

< 3% THD (EN 50091)

Overload Capability

– Inverter

125% for 10 minutes; 150% for 1 minute

– Bypass

200% for 2 minutes; 2000% for ½ cycle

Voltage Range

-25% / +20%

-20% / +15%

-15% / +10%

Frequency

60 Hz +/- 10%

Frequency

60 Hz (+/- 1%)

Dims ( W x D x H ) (inches) (UPS only)

22.7" x 30.7" x 51.6"

23.6" x 29.6" x 71.7 "

28.4" x 28.5" x 71.7"

39.4" x 35.4" x 75.0"

Input THD

< 8%

< 10%

Input Power Factor

> 0.98 lagging

Communication / Connectivity

RS

-232; programmable alarm contacts; open collector outputs; SNMP (optional)

Color

White (RAL 9003)

Warranty

Twelve (12) months after commissioning or eighteen (18) months after shipment, whichever occurs first *

Energy
Efficiency

Double Conversion

Up to 90%

Eco Mode

Up to 98%

Speci

fications subject to

change without notice.

* Extended Warranties

*

available

Technical Speci

fications

Represented by:

GE D

igital Energy –

Power Quality

830

W 40th Street

Chicago, IL 60609 USA

800 637 1738

www.gepowerquality.com

Information subject to change
without notice. Please verify
all details with GE.
© 2010 General Electric Company
All Rights Reserved

GEA

-D

2033 (4/10)

U

.

S

.-

B

ased

Customer Service