XPRT-6kVA XPRT-10kVA
Backup time 1/2 load Full load 1/2 load Full load
UPS
14 5 16 6
+ (1) BP
34
14
39
17
+ (2) BP
58
25
66
28
+ (3) BP
82
36
92
41
+ (4) BP
105
47
119
54
XPRT-6kVA
XPRT-10kVA
PDU1 = Hardwired
PDU3 = (4)5-20R + (2)L5-20R + (2)L6-30R
PDU2* = (4)5-20R + (1)L6-30R + (1)L14-30R PDU10 = (8)5-20R + (2)L6-30R
PDU4* = (2)5-20R + (2)L6-20R
PDU11 = (4)5-20R + (4)L6-20R
PDU5* = (4)5-20R + (2)L6-30R
PDU12 = (4)5-20R + (4)L6-30R
PDU6* = (4)EN60320
PDU13 = (4)5-20R + (2)L6-20R + (2)L6-30R
PDU7* = (4)L5-20R + (2)L5-30R
PDU14 = (4)L5-20R + (4)L6-20R
PDU8* = (4)L5-20R + (2)L6-30R
PDU9* = (4)L6-20R
Optional PDU provides
output receptacles
OPTIONAL INTEGRATED BYPASS/PDUs
BATTERY RUNTIMES
Optional SNMP card
Maintenance
bypass switch
Integrated bypass/
PDU modules
Input and output terminal
blocks for hardwired
connections
For more information, visit
www.xpcc.com/xprt6-10
MODEL SELECTION GUIDE
MODEL NUMBER
XPRT-6kVA XPRT-10kVA
INPUT
OUTPUT
BATTERY
PHYSICAL
ENVIRONMENT
Capacity VA (W)
6000VA (4200W)
10000VA (8000W)
Voltage 208/120V, 240/120V auto-sensing; 230/115V, 200/100V selectable*
Frequency
40
–
70Hz
Power factor
> 0.97
Input connection
10ft cord with L14–30P plug or hardwire
Hardwire
Voltage 208/120V, 240/120V, 230/115V, 200/100V (selectable) ± 5%
Frequency
50/60Hz auto-sensing ± 5% or frequency converter
Output connections Integrated bypass/PDU with hardwired or receptacle options (options below)
Harmonic distortion
< 3% with linear load; < 5% with non-linear load
Wave form
Sine wave, zero transfer time
Efficiency AC/DC/AC
> 92%
Auto restart/start on battery
Yes
Overload capacity
110% for 300 sec; 130% for 30 sec; 200% for 5 sec
Crest factor
3:1 at full load
Battery type
(12) 9AH/144VDC
(24) 9AH/288VDC
Recharge time
< 3 hours to 90%
UPS dimensions (W x D x H)
16.9 x 22.5 x 6.9 in (4U)
16.9 x 26.0 x 10.6 in (6U)
Weight with internal battery
162 lbs
309 lbs
Battery pack (BP) dimensions
16.9 x 22.5 x 3.5 in (2U)
16.9 x 26.0 x 6.8 in (4U)
Battery pack weight
95 lbs
200 lbs
Operating temperature
32–104°F (0–40°C)
Audible noise
< 55dba
Altitude
11,500 ft above sea level
APPROVALS
WARRANTY
COMMUNICATIONS INTERFACE
AVAILABLE OPTIONS
UL, cUL, FCC
3 years electronics and battery (2 years outside of USA)
RS-232, EPO, and USB standard, SNMP (optional card)
PDUs, parallel tie/bypass panels options available