beautypg.com

Technical specifi cations, Listed, Modular – MaxPower Corp GE GT Series 8 & 10kVA User Manual

Page 2: Lugs battery run times

background image

Model

GT8000 RT

GT10000 RT

Ratings

Power ratings depending on input voltage

VA / W

VA / W

100V / 200V :

6400 / 6400

8000 / 6400

110V / 220V :

7200 / 7200

9000 / 7200

115V / 230V :

8000 / 8000

10000 / 8000

120V / 208V :

8000 / 6900

8700 / 8000

120V / 240V :

8000 / 8000

10000 / 8000

127V / 220V :

8000 / 6900

8700 / 8000

Input thermal circuit breaker (A)

60

Internal input fuse 250V, slow (A) /Qty

30 / 2

Input converter

AC input voltage

Nominal: 120 / 208 V

AC input voltage range

100/(173-200), 110/(190-220), 115/(198-230),

120/(208-240), 127/(220) V

Input current waveform

sine wave

Input current (A) at nominal input voltage

40

Input power factor

> 0.97

Input frequency range

40 - 70 Hz

Input phase (L1 to L2)

120° / 180° / 240° ±10°

Inrush current

40

Output converter

AC output voltage

100 / 110 / 115 / 120 / 127 V (selectable)

AC output voltage tolerance

L-N ± 2%; L1-L2 ± 5%

Output frequency

50 / 60 Hz, auto selection

Output frequency range

nominal ± 5% with mains synchronizing

Output waveform

sine wave

Harmonic distortion

< 3% with linear load, < 5% with

non-linear full load

Power factor at nominal input voltage

0.86

0.92

Crest factor (peak to RMS current)

≤ 3 : 1

Capacity appliance outlets

with 55A Terminal Block

Bypass

AC input voltage range

± 15% of selected output voltage

Frequency tracking rate

1Hz/s

Frequency tracking range

± 5% of selected frequency

Typical transfer time, msec

0

Model

GT8000 RT

GT10000 RT

Overload capability

Overload behavior during
battery operation

130% for 1 minute

200% for 5 seconds

Overload behavior during
bypass operation

overload protection

110% of TCB value for 300 seconds

130% of TCB value for 30 seconds

200% of TCB value for 5 seconds

Batteries (ratings given for 25º C)

Nominal voltage (Vdc)

288

Qty / Ah (in battery kit and battery ext. pack)

24 / 8Ah

Type

REW45-12 FR

Recharge current

1 A

Battery recharge time
(batt. discharged at 100% load)

3 hours for 90% capacity

General

Weight UPS

49.3 Kg (109 lbs)

Dimensions UPS (HxWxD)

267x430x660 mm (10.5x16.9x26 in)

Weight battery pack

91 Kg (200.4 lbs)

Dimensions battery pack

173x430x660 mm (6.8x16.9x26 in)

Enclosure / protection

steel-plastic / IP20

Mounting

Rackmount or Tower mount with same unit

Environment

Safety Compliance

UL 1778

Electromagnetic compatibility

EMI: FCC CFR47 Part 15, class A, ESD:

IEC61000-4-2, level 4

RS: IEC61000-4-3, level 3, EFT: IEC61000-4-4,

level 4, Surge: IEC61000-4-5, level 3

ANSI C62.41 (IEEE587) Category A

(level 3) & B (level 1)

Ambient temperature

0 to +40ºC

Audible noise at 3.3 ft.

< 55 dB(A), load and temperature dependent

Max. relative humidity

90% (non-condensing)

Color

Black - RAL 9005

Technical Specifi cations –

UL

listed

Model

Outlets (NEMA)

5-20R T-type

L5-20R

L6-20R

L6-30R

L1-N-G

L2-N-G

L1-N-G

L2-N-G

L1-L2-G

L1-L2-G

GT PDU B 01

4

4

2

GT PDU B 02

2

2

4

GT PDU B 03

2

2

4

GT PDU B 04

2

2

2

2

GT PDU B 05

2

2

1

1

2

GT PDU B 06

2

2

4

Model

Load

Internal Batteries

1 Battery Pack

2 Battery Packs

3 Battery Packs

GT8000 RT / GT10000 RT

10%

107 min

251 min

333 min

494 min

25%

40 min

100 min

160 min

225 min

50%

16 min

39 min

66 min

92 min

75%

10 min

24 min

41 min

58 min

100%

6 min

17 min

28 min

41 min

Modular

PDU

P

lugs

Battery Run Times

U.S.-Based
Customer Service

GE

Digital Energy –

Power Quality
701 e 22nd Street
Lombard, IL

60148 USA

800 637 1738
www.gedigitalenergy.com/ups

Information subject to change
without notice. Please verify
all details with GE.
©

2009 General Electric Company

All Rights Reserved

Represented by:

DEA