Technical specifi cations, Listed, Modular – MaxPower Corp GE GT Series 8 & 10kVA User Manual
Page 2: Lugs battery run times
Model
GT8000 RT
GT10000 RT
Ratings
Power ratings depending on input voltage
VA / W
VA / W
100V / 200V :
6400 / 6400
8000 / 6400
110V / 220V :
7200 / 7200
9000 / 7200
115V / 230V :
8000 / 8000
10000 / 8000
120V / 208V :
8000 / 6900
8700 / 8000
120V / 240V :
8000 / 8000
10000 / 8000
127V / 220V :
8000 / 6900
8700 / 8000
Input thermal circuit breaker (A)
60
Internal input fuse 250V, slow (A) /Qty
30 / 2
Input converter
AC input voltage
Nominal: 120 / 208 V
AC input voltage range
100/(173-200), 110/(190-220), 115/(198-230),
120/(208-240), 127/(220) V
Input current waveform
sine wave
Input current (A) at nominal input voltage
40
Input power factor
> 0.97
Input frequency range
40 - 70 Hz
Input phase (L1 to L2)
120° / 180° / 240° ±10°
Inrush current
40
Output converter
AC output voltage
100 / 110 / 115 / 120 / 127 V (selectable)
AC output voltage tolerance
L-N ± 2%; L1-L2 ± 5%
Output frequency
50 / 60 Hz, auto selection
Output frequency range
nominal ± 5% with mains synchronizing
Output waveform
sine wave
Harmonic distortion
< 3% with linear load, < 5% with
non-linear full load
Power factor at nominal input voltage
0.86
0.92
Crest factor (peak to RMS current)
≤ 3 : 1
Capacity appliance outlets
with 55A Terminal Block
Bypass
AC input voltage range
± 15% of selected output voltage
Frequency tracking rate
1Hz/s
Frequency tracking range
± 5% of selected frequency
Typical transfer time, msec
0
Model
GT8000 RT
GT10000 RT
Overload capability
Overload behavior during
battery operation
130% for 1 minute
200% for 5 seconds
Overload behavior during
bypass operation
overload protection
110% of TCB value for 300 seconds
130% of TCB value for 30 seconds
200% of TCB value for 5 seconds
Batteries (ratings given for 25º C)
Nominal voltage (Vdc)
288
Qty / Ah (in battery kit and battery ext. pack)
24 / 8Ah
Type
REW45-12 FR
Recharge current
1 A
Battery recharge time
(batt. discharged at 100% load)
3 hours for 90% capacity
General
Weight UPS
49.3 Kg (109 lbs)
Dimensions UPS (HxWxD)
267x430x660 mm (10.5x16.9x26 in)
Weight battery pack
91 Kg (200.4 lbs)
Dimensions battery pack
173x430x660 mm (6.8x16.9x26 in)
Enclosure / protection
steel-plastic / IP20
Mounting
Rackmount or Tower mount with same unit
Environment
Safety Compliance
UL 1778
Electromagnetic compatibility
EMI: FCC CFR47 Part 15, class A, ESD:
IEC61000-4-2, level 4
RS: IEC61000-4-3, level 3, EFT: IEC61000-4-4,
level 4, Surge: IEC61000-4-5, level 3
ANSI C62.41 (IEEE587) Category A
(level 3) & B (level 1)
Ambient temperature
0 to +40ºC
Audible noise at 3.3 ft.
< 55 dB(A), load and temperature dependent
Max. relative humidity
90% (non-condensing)
Color
Black - RAL 9005
Technical Specifi cations –
UL
listed
Model
Outlets (NEMA)
5-20R T-type
L5-20R
L6-20R
L6-30R
L1-N-G
L2-N-G
L1-N-G
L2-N-G
L1-L2-G
L1-L2-G
GT PDU B 01
4
4
2
GT PDU B 02
2
2
4
GT PDU B 03
2
2
4
GT PDU B 04
2
2
2
2
GT PDU B 05
2
2
1
1
2
GT PDU B 06
2
2
4
Model
Load
Internal Batteries
1 Battery Pack
2 Battery Packs
3 Battery Packs
GT8000 RT / GT10000 RT
10%
107 min
251 min
333 min
494 min
25%
40 min
100 min
160 min
225 min
50%
16 min
39 min
66 min
92 min
75%
10 min
24 min
41 min
58 min
100%
6 min
17 min
28 min
41 min
Modular
PDU
P
lugs
Battery Run Times
U.S.-Based
Customer Service
GE
Digital Energy –
Power Quality
701 e 22nd Street
Lombard, IL
60148 USA
800 637 1738
www.gedigitalenergy.com/ups
Information subject to change
without notice. Please verify
all details with GE.
©
2009 General Electric Company
All Rights Reserved
Represented by:
DEA
-474 (9/09)