Technical specifi cations, Listed, Modular – MaxPower Corp GE GT Series 5 & 6kVA User Manual
Page 2: Lugs battery run times
Model
GT5000 RT
GT6000 RT
Ratings
Power ratings depending on input voltage
VA / W
VA / W
100V / 200V :
4000 / 3400
4800 / 3400
110V / 220V :
4500 / 3800
5400 / 3800
115V / 230V :
5000 / 4000
6000 / 4200
120V / 208V :
4800 / 4200
5200 / 4200
120V / 240V :
5000 / 4200
6000 / 4200
127V / 220V :
4800 / 4200
5200 / 4200
Input thermal circuit breaker (A)
30
Internal input fuse 250V, slow (A)
30
Input converter
AC input voltage
Nominal: 120 / 208 V
AC input voltage range
100/(173-200), 110/(190-220), 115/(198-230),
120/(208-240), 127/(220) V
Input current waveform
sine wave
Input current (A) at nominal input voltage
20
Input power factor
> 0.97
Input frequency range
40 - 70 Hz
Input phase (L1 to L2)
120° / 180° / 240° ±10°
Inrush current
40
Output converter
AC output voltage
100 / 110 / 115 / 120 / 127 V (selectable)
AC output voltage tolerance
L-N ± 3%; L1-L2 ± 5%
Output frequency
50 / 60 Hz, auto selection
Output frequency range
nominal ± 5% with mains synchronizing
Output waveform
sine wave
Harmonic distortion
< 3% with linear load, < 5% with
non-linear full load
Power factor at nominal input voltage
0.87
0.8
Crest factor (peak to RMS current)
≤ 3 : 1
Capacity appliance outlets
with 55A Terminal Block
Bypass
AC input voltage range
± 15% of selected output voltage
Frequency tracking rate
1Hz/s
Frequency tracking range
± 5% of selected frequency
Typical transfer time, msec
0
Model
GT5000 RT
GT6000 RT
Overload capability
Overload behavior during
battery operation
130% for 10 seconds
200% for 2 seconds
Overload behavior during
bypass operation
depends on rating of
thermal circuit breaker (TCB)
125% of TCB value for 200 seconds
200% of TCB value for 10 seconds
300% of TCB value for 4 seconds
Batteries (ratings given for 25º C)
Nominal voltage (Vdc)
144
Qty/ Ah (in battery kit and battery ext. pack)
12 pcs / 8Ah
Type
REW45-12 FR
Recharge current
1 A
Battery recharge time
(batt. discharged at 100% load)
6 hours for 90% capacity
General
Weight UPS
30.3 Kg (67 lbs)
Dimensions UPS (HxWxD)
176x430x592 mm (6.9x16.9x22.55 in)
Weight battery pack
43 Kg (94.7 lbs)
Dimensions battery pack
87x430x592 mm (3.47x16.9x2255 in)
Enclosure / protection
steel-plastic / IP20
Mounting
Rackmount or Tower mount with same unit
Environment
Safety Approval
UL 1778
Electromagnetic compatibility
EMI: FCC CFR47 Part 15, class A, ESD:
IEC61000-4-2, level 4
RS: IEC61000-4-3, level 3, EFT: IEC61000-4-4,
level 4, Surge: IEC61000-4-5, level 3
ANSI C62.41 (IEEE587) Category A
(level 3) & B (level 1)
Ambient temperature
0 to +40ºC
Audible noise at 3.3 ft.
< 55 dB(A), load and temperature dependent
Max. relative humidity
90% (non-condensing)
Color
Black - RAL 9005
Technical Specifi cations –
UL
listed
Model
Outlets (NEMA)
Input (NEMA)
TB**
5-20R T
L5-20R
L5-30R
EN60320
L6-20R
L6-30R
L14-30R
TB**
L14-30R
L1-N-G
L2-N-G
L1-N-G
L2-N-G
L1-N-G
L2-N-G
L1-N-G
L2-N-G
L1-L2-G
L1-L2-G
L1-N-L2-G
GT PDU A 01*
1
1
GT PDU A 02
1
1
GT PDU A 03
2
2
1
1
1
GT PDU A 04
1
1
2
1
GT PDU A 05
2
2
2
1
GT PDU A 06
2
2
1
GT PDU A 07
2
2
1
1
1
GT PDU A 08
2
2
2
1
GT PDU A 09
4
1
Model
Load
Internal Batteries
1 Battery Pack
2 Battery Packs
3 Battery Packs
GT5000 RT / GT6000 RT
10%
75 min
156 min
235 min
313 min
25%
31 min
75 min
115 min
155 min
50%
14 min
34 min
58 min
82 min
75%
8 min
22 min
35 min
50 min
100%
5 min
14 min
25 min
36 min
Modular
PDU
P
lugs
Battery Run Times
*: No 3 pole 6 ms maximum transfer time manual bypass. **: TB = Terminal Block
GE
Digital Energy –
Power Quality
701 e 22nd Street
Lombard, IL
60148 USA
800 637 1738
www.gedigitalenergy.com/ups
Information subject to change
without notice. Please verify
all details with GE.
©
2009 General Electric Company
All Rights Reserved
Represented by:
DEA
-473 (9/09)
U.S.-Based
Customer Service