beautypg.com

Options – MaxPower Corp GE IT Series _ 600VA-2kVA tower User Manual

Page 2

background image

Model Number

UPS0600ITSIT

UPS1000ITSIT

UPS1500ITSIT

UPS2000ITSIT

Power Rating

Output Capacity

600VA / 360W

1000VA / 600W

1500VA / 900W

2000VA / 1200W

Power Factor

Output Power Factor

0.6 pf

Input

Voltage

120V +/- 10% at line input, single phase

Frequency

50 or 60 Hz +/- 5Hz auto-sensing

Input Power Connection

Detachable 5-15P

Detachable 5-15P

Hardwired 5-15P

Hardwired 5-20P

Output

Voltage

(on Battery)

Pure sine wave at +/- 5% of nominal, -10% of nominal after low battery warning

Voltage

(on Mains)

120V, -12%/+10%

Voltage THD

< 5% @ 100% resistive load with 80% battery capacity

Frequency

(on Battery)

50 or 60 Hz +/- 5% auto-sensing

Voltage Regulation (AVR)

AVR

automatically increases (boost) output voltage 17% above input voltage if -9% to -25% of nominal.

AVR

decreases (buck) output voltage 14% below input voltage if +9% to +25% of nominal.

Output Receptacles -

Power Distribution

(4) 5-15R

(4) 5-15R

(6) 5-15R

(6) 5-15R

Protection &

Filtering

Spike Protection

780 Joules/6500A

EMI

/RF Filter

10dB @ 0.15MHz, 50 dB @ 30 MHz

Overload Protection

UPS

automatic shutdown if overload exceeds 110% of nominal @ 20 seconds and 125% @ 5 seconds

Transfer Time

4/6 milliseconds

(typical)

, including detection time

Short Circuit

Active protection with automatic shutdown

Battery

System Type

Hot swappable, sealed Valve Regulated Lead Acid (VRLA)

Battery

12V / 9.0 AH

Typical Recharge Time

4 hours

(to 90% of full capacity)

Protection

Automatic self-test and discharge protection, Replace battery indicator

Battery Quantity

2 pcs

2 pcs

3 pcs

4 pcs

Net Weight

(lbs)

30.4 lbs

33.0 lbs

55.0 lbs

66.0 lbs

Dimensions

W x D x H (Inches)

5.5" x 17.2" x 8.3"

5.5" x 17.2" x 8.3"

6.7" x 17.7" x 8.9"

6.7" x 17.7" x 8.9"

Communi-

cations

RS

-232

Standard (Detect battery low, schedule UPS on/off, AC Input/Output power status display)

USB

Standard

SNMP

Optional

Operating System

Windows NT, Windows 2000/ME, Windows XP, Linux

Environment

Ambient operation

3,500 meters max. elevation, 0-95% RH non-condensing, 0-40

°

C

Audible noise @ 1 meter

< 40 dBA

< 45 dBA

Storage condition

15,000 meters max. elevation, 0-95% RH non-condensing, 0-40

°

C

Certi

fications

UL, cUL, FCC Class A

Battery Runtimes

(minutes) ***

VA

Standard Internal Battery System

@ 25% Load

@ 50% Load

@ 75% Load

@ 100% Load

600

84

35

20

14

1000

42

17

10

6

1500

42

17

10

6

2000

42

17

10

6

*** Runtimes are estimated

Options

>

SNMP

communication cards are available

and sold separately

> For replacement batteries, please contact

the

UPS P

arts Department: 800 637 1738

* See

UPS

Limited Warranty Rider, Publication No. GETCPQ-UPS

** Contact a factory representative: 800 637 1738

> Extended Limited Product Warranties Available **

1 Year

3 Year

5 Year

Represented by:

GE

Energy – Digital Energy

830

W 40th Street

Chicago, IL 60609 USA

800 637 1738

www.gepowerquality.com

Information subject to change
without notice. Please verify
all details with GE.
© 2010 General Electric Company
All Rights Reserved

DEA

-