MITSUBISHI ELECTRIC POWER PRODUCTS, INC.
n
THE DIAMONDPLUS™ 1100A AND 1100B UPS SERIES
Superior UPS Technology for Mission Critical Applications
THE DIAMONDPLUS™ 1100A AND 1100B UPS SERIES
n
MITSUBISHI ELECTRIC POWER PRODUCTS, INC.
3
AC Input
n
Input Power:
208V/120V, 3P, 4W, 60 Hz
(Other voltages available with external
transformers)
n
Voltage Range:
+15%, -30%
n
Reflected Current Harmonic
Distortion (THD):
4% @ 100% load
7% @ 50% load (Typical)
n
Power Factor:
0.98 at 50% and 100% load
n
Surge Withstand:
Meets IEEE 587, ANS/IEEE 62.41,
Category B
Common Specifications:
* Modules are not exchangeable between 1100A and 1100B
* Cable entry for 1100B is on right side, top, and bottom
Distinct Specifications:
1100A
1100B
kVA 10 - 50
10 - 80
Batteries 10 & 20 kVA: Interior
10-80 kVA: external cabinet
30-50 kVA: external cabinet required
required
Dimensions 55.1"H x 19.7"W x 27.0"D
67.3"H x 31.5"W x 27.0"D
Weight 685 (10 kVA, with internal batteries) –
498 (10 kVA) – 807 (80 kVA)
(lbs) 465 (50 kVA, without internal batteries)
(without internal batteries)
Standard Features
n
Fully-digital IGBT converter and
inverter
n
Hot swappable modules
n
Pulse Width Modulation
(PWM) controls
n
On-line upgradable
n
Front access UPS
n
Small footprint and lightweight
n
UL 1778 listed
Operating Environment
n
Audible Noise:
58 dB @ 1 Meter
n
Temperature:
0-40º C
n
Relative Humidity:
5-95% (Non-condensing)
n
Altitude:
0-5,000 ft.
AC Output
n
Output Power:
208V/120V, 4W, 60 Hz
n
Power Factor: 0.9
n
Voltage Regulation:
+/-1% Balanced
+/-2% Unbalanced loads
n
Frequency Regulation:
60 Hz +/-0.01%
n
Step Load:
(100%) +/- 3% variation, recovery less
than one cycle
n
Voltage THD:
2% Maximum @ 100% Linear Load
5% @ Nonlinear Load
n
Overload:
105-125% -60 sec
126-150% -30 sec
n
EMI Compatibility:
FCC Article 47, Part 15 Subpart B,
Class A
19.69
500
55.13
1400
MITSUBISHI
31.50
800
67.32
1710
62.64
1591
MITSUBISHI
1100A: