Dsca, High performance signal conditioners, Dsca specifications – Impulse DSCA32 User Manual
Page 2: Ordering information
High Performance Signal Conditioners
DSCA
Visit our website www.dataforth.com
133
DSCA
Specifications
Input Range
0-20mA or 4-20mA
Input Resistance
Normal
<100
Ω
Power Off
<100
Ω
Overload
65k
Ω
Input Protection
Continuous
240Vrms max
Transient
ANSI/IEEE C37.90.1
Output Range
See Ordering Information
Load Resistance (I
OUT
)
600
Ω
max
Current Limit
8mA (V
OUT
), 30mA (I
OUT
)
Output Protection
Short to Ground
Continuous
Transient
ANSI/IEEE C37.90.1
CMV, Input to Output, Input to Power
Continuous
1500Vrms max
Transient
ANSI/IEEE C37.90.1
CMV, Output to Power
Continuous
50VDC max
CMR (50Hz or 60Hz)
105dB
Accuracy
(1)
±0.03% Span
Nonlinearity
±0.01% Span
Adjustability
±5% Zero and Span
Stability
Offset
±6ppm/°C (V
OUT
), ±20ppm/°C (I
OUT
)
Gain
±40ppm/°C
Output Noise, 100kHz Bandwidth
300µVrms (V
OUT
), 1.2µArms (I
OUT
)
Bandwidth, 3dB
100Hz
NMR (-3dB at 100Hz)
100dB/decade Above 100Hz
Response Time, 90% Span
5ms
Power Supply
Voltage
15 to 30VDC
Current
25mA (V
OUT
), 55mA (I
OUT
)
Sensitivity
±0.0001%/%
Protection
Reverse Polarity
Continuous
Transient
ANSI/IEEE C37.90.1
Environmental
Operating Temp. Range
40°C to +80°C
ATEX Group II, Category 3
20°C to +40°C
Storage Temp. Range
40°C to +80°C
Relative Humidity
0 to 95% Noncondensing
Emissions EN61000-6-4
ISM, Group 1
Radiated, Conducted
Class A
Immunity EN61000-6-2
ISM, Group 1
RF
Performance A ±0.05% Span Error
ESD, EFT, Surge, Voltage Dips
Performance B
Mechanical Dimensions
2.95" x 0.89" x 4.13"
(h)(w)(d)
(75mm x 22.5mm x 105mm)
Mounting
DIN EN 50022 -35x7.5 or -35x15 rail
Module
DSCA32
NOTES:
(1) Includes nonlinearity, hysteresis and repeatability.
Typical at T
A
=+25°C and +24V supply voltage
Ordering Information
Model
Input Range
Output Range
DSCA32-01
4mA to 20mA
2, 3, 4
DSCA32-02
0mA to 20mA
2, 3, 4
DSCA32-03
±20mA
1
DSCA32-04
±20mA
2, 3, 4
Installation Notes:
1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B, C, D, or Non-Hazardous Locations Only.
2.) Warning - Explosion Hazard - Substitution of Components May Impair Suitability for Class I, Division 2.
3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless Power Has Been Switched Off or The
Area is Known to be Non-Hazardous.
1. -10V to +10V
NONE
DSCA32-03
2. 0V to +10V
NONE
DSCA32-01
3.
4 to 20mA
C
DSCA32-01C
4.
0 to 20mA
E
DSCA32-01E
Output Range Part No. Suffix Example
Output Ranges Available