Dsca, High performance signal conditioners, Dsca specifications – Impulse DSCA33 User Manual
Page 2: Ordering information
High Performance Signal Conditioners
DSCA
Visit our website www.dataforth.com
135
DSCA
Specifications
Input
Signal Range
100mV to 300Vrms, 0 to 5Arms
Standard Frequency Range
45Hz to 1000Hz
Extended Frequency Range
1kHz to 20kHz
Impedance
1 M
Ω
±1% // <100pF (-01 thru -05), 0.10
Ω
(-06), 0.025
Ω
(-07)
Coupling
AC
Protection
Continuous (-01 thru -05)
480V peak AC & DC max
Continuous (-06 thru -07)
10 Arms max
Transient (-01 thru -05)
ANSI/IEEE C37.90.1
Transient (-06 thru -07)
See note 1
Output
Signal Range
See Ordering Information
Adjustability
±5% Zero & Span
Load Resistance
10k
Ω
max. (0-1mA models), 600
Ω
max. (0/4-20mA models)
Current Limit
1.4mA (0-1mA models), 30mA (0/4-20mA models),
8mA (0-5/10V models)
Protection
Short to Ground
Continuous
Transient
ANSI/IEEE C37.90.1
Ripple and Noise
<0.025% Span rms
Accuracy
(2) (3)
Sinusoid
50/60Hz
±0.25% Span
45Hz-1kHz
±0.25% Reading Additional Error
1kHz-20kHz
±0.75% Reading Additional Error
Non-Sinusoid
Crest Factor = 1 to 2
±0.05% Reading Additional Error
Crest Factor = 2 to 3
±0.15% Reading Additional Error
Crest Factor = 3 to 4
±0.30% Reading Additional Error
Crest Factor = 4 to 5
±0.40% Reading Additional Error
Vs. Temperature
±100ppm/°C
Isolation (Common Mode)
Input to Output, Input to Power
Continuous
1500Vrms max
Transient
ANSI/IEEE C37.90.1
Output to Power
Continuous
50VDC max
Response Time (0 to 99%)
<400ms
CMR (50 or 60Hz)
100dB
Power Supply
Voltage
19 to 29VDC
Current
60mA (V
OUT
), 80mA (I
OUT
)
Sensitivity
±0.0002%/%
Protection
Reverse Polarity
Continuous
Transient
ANSI/IEEE C37.90.1
Environmental
Operating Temp. Range
-40°C to +80°C
ATEX Group II, Category 3
-20°C to +40°C
Storage Temp. Range
-40°C to +80°C
Relative Humidity
0 to 95% noncondensing
Emissions EN61000-6-4
ISM, Group 1
Radiated, Conducted
Class A
Immunity EN61000-6-2
ISM, Group 1
RF
Performance A ±0.83% Span Error
ESD, EFT, Surge, Voltage Dips
Performance B
Mechanical Dimensions (h)(w)(d)
2.95" x 0.89" x 4.13" (75mm x 22.5mm x 105mm)
Mounting
DIN EN50022-35x7.5 or -35x15 rail
Module
DSCA33
Typical at T
A
=+25°C and +24V supply voltage
Model
Input (rms)
Output (dc)
DSCA33-01
0-100mV
2, 3, 4, 5, 6
DSCA33-02
0-1V
2, 3, 4, 5, 6
DSCA33-03
0-10V
2, 3, 4, 5, 6
DSCA33-04
0-150V
2, 3, 4, 5, 6
DSCA33-05
0-300V
2, 3, 4, 5, 6
DSCA33-06
0-1A
2, 3, 4, 5, 6
DSCA33-07
0-5A
2, 3, 4, 5, 6
Ordering Information
Modules can be ordered with other input/output ranges. Consult
factory for ordering details and specifications
Installation Notes:
1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B,
C, D, or Non-Hazardous Locations Only.
2.) Warning - Explosion Hazard - Substitution of Components May Impair
Suitability for Class I, Division 2.
3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless
Power Has Been Switched Off or The Area is Known to be Non-Hazardous.
NOTES:
(1) For 1 to 25 seconds the max allowable transient current rating is
√
2500 / (event time). For less than 1 second,
ANSI/IEEE C37.90.1 applies with a 0.05
Ω
load. For greater than 25 seconds, the 10A max continuous rating applies.
(2) For 10-100% rated span. Add 0.25% accuracy error (-02 thru -07), or 1.00% accuracy error (-01), for 0-10% Span measurements.
Accuracy includes nonlinearity, hysteresis and repeatability but not source or external shunt inaccuracy (if used).
(3) At standard 60Hz factory calibration. Consult factory for calibration at other frequencies.
2. 0V to +10V
NONE
DSCA33-01
3.
4 to 20mA
C
DSCA33-01C
4.
0 to 20mA
E
DSCA33-01E
5. 0V to +5V
A
DSCA33-01A
6.
0 to 1mA
B
DSCA33-01B
Output Range Part No. Suffix Example
Output Ranges Available