Dsca, High performance signal conditioners, Dsca specifications – Impulse DSCA40_41 User Manual
Page 2: Ordering information

High Performance Signal Conditioners
DSCA
Visit our website www.dataforth.com
147
DSCA
Specifications
Model
DSCA40
DSCA41
Input Range
+10mV to +100mV
±1V to ±40V
Input Bias Current
±0.5nA
±0.05nA
Input Resistance
Normal
50M
Ω
500k
Ω
min
Power Off
65k
Ω
500k
Ω
min
Overload
65k
Ω
500k
Ω
min
Input Protection
Continuous
240Vrms max
*
Transient
ANSI/IEEE C37.90.1
*
Output Range
See Ordering Information
Load Resistance (I
OUT
)
600
Ω
max
*
Current Limit
8mA (V
OUT
), 30mA (I
OUT
)
Output Protection
Short to Ground
Continuous
*
Transient
ANSI/IEEE C37.90.1
*
CMV, Input to Output, Input to Power
Continuous
1500Vrms max
*
Transient
ANSI/IEEE C37.90.1
*
CMV, Output to Power
Continuous
50VDC max
*
CMR (50Hz or 60Hz)
100dB
*
Accuracy
(1)
±0.03% Span
*
Nonlinearity
±0.01% Span
*
Adjustability
±5% Zero and Span
*
Stability
Input Offset
±0.5µV/°C
±5µV/°C
Output Offset
±6ppm/°C (V
OUT
), ±20ppm/°C (I
OUT
)
*
Zero Suppression
±50ppm(V
z
)
(2)
/°C
*
Gain
±35ppm/°C
±55ppm/°C
Output Noise, 100kHz Bandwidth
750µVrms (V
OUT
), 3µArms (I
OUT
)
*
Bandwidth, 3dB
3kHz
*
NMR
100dB/decade above 3kHz
*
Response Time, 90% Span
170µs
*
Power Supply
Voltage
15 to 30VDC
*
Current
25mA (V
OUT
), 55mA (I
OUT
)
*
Sensitivity
±0.0001%/%
*
Protection
Reverse Polarity
Continuous
*
Transient
ANSI/IEEE C37.90.1
*
Environmental
Operating Temp. Range
40°C to +80°C
*
ATEX Group II, Category 3
20°C to +40°C
*
Storage Temp. Range
40°C to +80°C
*
Relative Humidity
0 to 95% Noncondensing
*
Emissions EN61000-6-4
ISM, Group 1
*
Radiated, Conducted
Class A
*
Immunity EN61000-6-2
ISM, Group 1
*
RF
Performance A ±0.05% Span Error
*
ESD, EFT, Surge, Voltage Dips
Performance B
*
Mechanical Dimensions
2.95" x 0.89" x 4.13"
*
(h)(w)(d)
(75mm x 22.5mm x 105mm)
Mounting
DIN EN 50022 -35x7.5
*
or -35x15 rail
Model
Input Range
Output Range
DSCA40-01
-10mV to +10mV
1
DSCA40-02
-50mV to +50mV
1
DSCA40-03
-100mV to +100mV
1
DSCA40-04
-10mV to +10mV
2, 3, 4
DSCA40-05
-50mV to +50mV
2, 3, 4
DSCA40-06
-100mV to +100mV
2, 3, 4
DSCA40-07
0 to +10mV
2, 3, 4
DSCA40-08
0 to 50mV
2, 3, 4
DSCA40-09
0 to +100mV
2, 3, 4
DSCA41-01
-1V to +1V
1
DSCA41-02
-5V to +5V
1
DSCA41-03
-10V to +10V
1
DSCA41-04
-1V to +1V
2, 3, 4
DSCA41-05
-5V to +5V
2, 3, 4
DSCA41-06
-10V to +10V
2, 3, 4
DSCA41-07
-20V to +20V
1
DSCA41-08
-20V to +20V
2, 3, 4
DSCA41-09
-40V to +40V
1
DSCA41-10
-40V to +40V
2, 3, 4
DSCA41-11
0 to +1V
2, 3, 4
DSCA41-12
0 to +5V
2, 3, 4
DSCA41-13
0 to +10V
2, 3, 4
DSCA41-14
0 to +20V
2, 3, 4
DSCA41-15
0 to +40V
2, 3, 4
Ordering Information
Typical at T
A
=+25°C and +24V supply voltage
Output Range
Part No. Suffix
Example
1. -10V to +10V
NONE
DSCA40-01
2. 0V to +10V
NONE
DSCA40-04
3. 4 to 20mA
C
DSCA40-04C
4. 0 to 20mA
E
DSCA40-04E
Output Ranges Available
Installation Notes:
1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B, C, D, or Non-Hazardous Locations Only.
2.) Warning - Explosion Hazard - Substitution of Components May Impair Suitability for Class I, Division 2.
3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless Power Has Been Switched Off or The
Area is Known to be Non-Hazardous.
NOTES:
* Same specification as DSCA40.
(1) Includes nonlinearity, hysteresis and repeatability.
(2) V
z
is the nominal input voltage that results in 0V or 0mA output.