Scm7b, Scm7b specifications, Ordering information – Impulse SCM7B39 User Manual
Page 2

SCM7B
Visit our website www.dataforth.com
81
Isolated Process Control Signal Conditioning Products
SCM7B
Specifications
Typical at 25°C and +24VDC
Output
Signal Range
(1)
4-20mA, 0-20mA
4-20mA
Effective Available Power
(1)
320mW
*
Protection
Continuous
120Vrms max
*
Transient
ANSI/IEEE C37.90.1
*
Current Limit
32mA
*
Input
Signal Range
1 to +5V, 0 to +10V
4-20mA
Bias Current
±1nA
N/A
Resistance
Normal
10M
Ω
270
Ω
Power Off
30k
Ω
min
>20k
Ω
Overload
30k
Ω
min
N/A
Protection
±35Vpeak (no damage)
±7.5Vpeak
Compliance
N/A
35VDC max
CMV (Input-to-Output)
Continuous
1500Vrms
*
Transient
ANSI/IEEE C37.90.1
*
CMRR (50 or 60Hz)
110dB
*
Accuracy
(2)
±0.03% Span typical,
*
±0.1% Span max
Nonlinearity
(3)
±0.01% Span typical,
*
±0.02% Span max
Stability (-40°C to +85°C)
Gain
±25ppm/°C
±50ppm/°C
Output Offset
±0.0035% Span/°C
±0.0045% Span/°C
Noise
Peak at 5MHz B/W
46µA
*
RMS at 10Hz to 100kHz B/W
4µA
*
Peak at 0.1Hz to 10Hz B/W
42nA
*
Open Output Loop Detection
Response
N/A
Input Resistance
> 20k
Ω
Detection Time
N/A
5ms
Frequency and Time Response
Bandwidth, -3dB
100Hz
*
NMR (-3dB at 100Hz)
80dB per decade above 100Hz
*
Step Response, 90% Span
5ms
*
Supply Voltage
18 to 35VDC
*
Current
(1)
56mA
*
Sensitivity
±0.0003%/%V
S
*
Mechanical Dimensions
2.13" x 1.705" x 0.605" max
*
(h)(w)(d)
54.1mm x 43.3mm x 15.4mm max
*
Environmental
Operating Temperature Range
-40°C to +85°C
*
ATEX Group II, Category 3
-20°C to +40°C
*
Storage Temperature Range
-40°C to +85°C
*
Relative Humidity
0 to 95% noncondensing
*
Emissions EN61000-6-4
ISM, Group 1
*
Radiated, Conducted
Class A
*
Immunity EN61000-6-2
ISM, Group 1
*
RF
Performance A ±0.5% Span Error
*
ESD, EFT, Surge, Voltage Dips
Performance B
*
Module SCM7B39-01,-02,-03 SCM7B39-04
Ordering Information
Model
Input Range
Output Range
NOTES:
* Same specification as SCM7B39-01, -02, -03
(1) Output Range and Supply Current specifications are based on maximum output load resistance. Maximum output
load resistance is calculated by P
E
/I
OUT
2
where P
E
is the Output Effective Available Power that guarantees output range,
accuracy, and linearity specifications. Output effective available power is independent of supply voltage.
(2) Accuracy includes the effects of repeatability, hysteresis, and linearity.
(3)
Nonlinearity is calculated using the best-fit straight line method.
SCM7B39-01
+1 to +5V
4 to 20mA
SCM7B39-02
0 to +10V
0 to 20mA
SCM7B39-03
0 to +10V
4 to 20mA
SCM7B39-04
4 to 20mA
4 to 20mA