Scm7b, Scm7b specifications, Ordering information – Impulse SCM7B36 User Manual
Page 2
SCM7B
Visit our website www.dataforth.com
77
Isolated Process Control Signal Conditioning Products
SCM7B
Specifications
Input Range
(See Ordering Information)
Protection
Continuous
120Vrms max
Transient
ANSI/IEEE C37.90.1
Sensor Excitation Current
65µA (10k
Ω
) to 260µA (100
Ω
)
Lead Resistance Effect (3-Wire)
(1)
-01 thru -04 : ±0.005
Ω
/
Ω
-05
: ±0.02
Ω
/
Ω
-06
: ±0.04
Ω
/
Ω
Output Range
(2)
(See Output Range)
Effective Available Power
(2)
40mW
Resistance
< 1
Ω
Protection
Continuous Short-to-Ground
Voltage/Current Limit
±12V, ±14mA
CMV (Input to Output)
Continuous
1500Vrms
Transient
ANSI/IEEE C37.90.1
CMRR (50 or 60Hz)
120dB
Accuracy
(3)
±0.03% Span typical,
±0.1% Span max
Nonlinearity
(4)
±0.01% Span typical,
±0.02% Span max
Stability (-40°C to +85°C)
Input Offset
±0.01
Ω
/°C
Output Offset
±30µV/°C
Gain
±60ppm/°C
Noise Peak at 5MHz B/W
1mV
RMS at 10Hz to 100kHz B/W
250µV
Peak at 0.1Hz to 10Hz B/W
1µV RTI
Open Input Response
+ Lead
Upscale
Lead
Non-deterministic
x Lead
Downscale
Open Input Detection Time
<5s
Frequency and Time Response
Bandwidth, -3dB
3Hz
NMR (50/60Hz)
80/85dB
Step Response, 0 to 90%
250ms
Supply Voltage
14-35VDC
Current
2
12mA
Sensitivity
±0.0001%/%V
S
Mechanical Dimensions
2.13" x 1.705" x 0.605", max
(h)(w)(d)
54.1mm x 43.3mm x 15.4mm max
Environmental
Operating Temp. Range
-40°C to +85°C
ATEX Group II, Category 3
-20°C to +40°C
Storage Temp. Range
-40°C to +85°C
Relative Humidity
0 to 95% Noncondensing
Emissions EN61000-6-4
ISM, Group 1
Radiated, Conducted
Class A
Immunity EN61000-6-2
ISM, Group 1
RF
Performance A ±0.5% Span Error
ESD, EFT, Surge, Voltage Dips
Performance B
Module
SCM7B36
Typical at 25°C and +24VDC
NOTES:
(1) Lead resistance effect is given for the condition of not having the NTC thermistor installed in the
backpanel. As a general rule; as long as the lead resistance of the (+) lead matches the parallel
combination of the thermistor and lead resistance in the (X) lead, the given specifications apply.
(2) Output Range and Supply Current specifications are based on minimum output load resistance.
Minimum output load resistance is calculated by V
OUT
2
/P
E
, where P
E
is the output Effective Available
Power that guarantees output range and accuracy specifications.
(3) Accuracy includes the effects of repeatability, hysteresis, and linearity, but does not include sensor
accuracy.
(4) Nonlinearity is calculated using the best-fit straight line method.
Ordering Information
Model
Input Range
SCM7B36-01
0 - 100
Ω
SCM7B36-02
0 - 200
Ω
SCM7B36-03
0 - 500
Ω
SCM7B36-04
0 - 1k
Ω
SCM7B36-05
0 - 5k
Ω
SCM7B36-06
0 - 10k
Ω
Output Range Part No. Suffix
Example
+1 to +5V
NONE
SCM7B36-01
0 to +5V
A
SCM7B36-01A
0 to +10V
D
SCM7B36-01D
Output Ranges Available