Description
The SCM7B32 current input modules accept input signals in the 4-20mA or 0-
20mA ranges from the field and provide a high level output to the process control
system (Figure 1). Current to voltage conversion occurs internal to the module,
which is factory calibrated to ensure the highest accuracy.
SCM7B33 voltage input modules accept input signals in the +1V to +5V or 0 to
+5V ranges from the field and provide a high level output to the process
control system. As an alternative, the SCM7B33 can be used with an external
250
Ω
resistor (Dataforth SCM7BXR1 or equivalent), to accept input signals in
the 4-20mA or 0-20mA ranges. Using the external sense resistor allows the
module to be removed without disrupting the current loop. All SCM7B33s are
shipped with a SCM7BXR1 resistor.
These modules incorporate a five-pole filtering approach to maximize both time
and frequency response by taking advantage of both Thomson (Bessel) and
Butterworth characteristics. One pole of the filter is on the field side of the isolation
barrier; four are on the process control system side.
After the initial field-side filtering (conversion-SCM7B32 only), the input signal
is chopped by a proprietary chopper circuit and transferred across the
transformer isolation barrier, suppressing transmission of common mode spikes
and surges. The signal is then reconstructed and filtered for process control
system output.
Modules accept a wide 14 - 35VDC power supply range (+24VDC nominal).
Their compact packages (2.13"x1.705"x0.605" max) save space and are ideal
for high channel density applications. They are designed for easy DIN rail
mounting using any of the -DIN backpanels.
Figure 1: SCM7B32/33 Block Diagram
▲
Features
Accepts Current or Voltage Input
Provides High Level Voltage Outputs
1500Vrms Transformer Isolation
Accuracy, ±0.03% of Span Typical,
±0.1% Max
ANSI/IEEE C37.90.1 Transient Protection
Input Protected to 120Vrms Continuous
Noise, 500µV Peak (5MHz), 300µV RMS
(100kHz)
CMRR, up to 105dB
80dB Per Decade of Attenuation
Above 100Hz
Easy DIN Rail Mounting
CSA Certified, FM Approved
CE and ATEX Compliant