beautypg.com

Impulse SCM7B34_34N User Manual

Isolated linearized 2- or 3-wire rtd input modules, Scm7b

background image

Isolated Process Control Signal Conditioning Products

SCM7B

For information call 800-444-7644

72

SCM7B34/34N

Isolated Linearized 2- or 3-Wire RTD Input Modules

Description

Each SCM7B34/34N RTD input module accepts a single channel of 100

Platinum (

α

= 0.00385) or 120

Nickel (

α

= 0.00672) RTD input and produces

an input voltage in response to a low level current excitation. The input signal

is filtered, isolated, amplified, linearized, and converted to a high level analog

voltage for output to the process control system (Figure 1).
These modules incorporate a five-pole filtering approach to maximize both time

and frequency response by taking advantage of both Thomson (Bessel) and

Butterworth characteristics. One pole of the filter is on the field side of the isolation

barrier; four are on the process control system side.
In response to the low level current excitation signal, the RTD input signal is

chopped by a proprietary chopper circuit and transferred across the trans-

former isolation barrier, suppressing transmission of common mode spikes and

surges. The signal is then reconstructed and filtered for process control system

output.
Linearization is achieved by creating a non-linear transfer function through the

module itself. This non-linear transfer function is configured at the factory and

is designed to be equal and opposite to the specific RTD non-linearity. Lead

compensation is achieved by matching two current paths thus cancelling the

effects of lead resistance.
Modules accept a wide 14 - 35VDC power supply range (+24VDC nominal).

Their compact packages (2.13"x1.705"x0.605" max) save space and are ideal

for high channel density applications. They are designed for easy DIN rail

mounting using any of the “-DIN” backpanels.

Figure 1: SCM7B34/34N Block Diagram

Features

• Interfaces to 100

Platinum or 120

Nickel RTDS

• Provides 250µA RTD Excitation Current
• Linearizes RTD Signal Response
• Provides High Level Voltage Outputs
• 1500Vrms Transformer Isolation
• Accuracy, ±0.05% to ±0.15% of

Span Typical

• Nonconformity, ±0.025% to ±0.07% of

Span Typical

• ANSI/IEEE C37.90.1 Transient Protection
• Input Protected to 120Vrms Continuous
• Noise, 500µV Peak (5MHz), 250µV RMS

(100kHz)

• CMRR, up to 160dB
• NMR, up to 85dB
• Easy DIN Rail Mounting
• CSA Certified, FM Approved
• CE and ATEX Compliant