Dscp, Isolated analog signal conditioning products, Ordering information installation – Impulse DSCP70 User Manual

Page 2: Dimensional drawing specifications

background image

2

2

Isolated Analog Signal Conditioning Products

DSCP

©

1995-2010 Dataforth Corporation, All Rights Reserved ISO9001:2008-Registered QMS

Visit our website www.dataforth.com

Model

Description

DSCP70

Power Supply Connection Module

DSCX-02

DIN Rail Expandable Power-Bus Connector

Ordering Information

Installation

3.67“ (93.1mm)

4.04

“ (102.5mm)

0.24“

(6.2mm)

Dimensional Drawing

Specifications

Typical at T

A

=+25°C and +24VDC power

Module

DSCP70

Input

Voltage

19.2 to 30VDC

Current Capacity

4A maximum per terminal

Protection

Each positive input must have an external

fuse

Output
Internal Voltage Drop

300mV

Current Capacity

One input = 1.6A

parallel inputs 1 and 2 = 2A

Filter

Differential mode: 4.7mH and two 470nF

per input

Power Consumption

5mA per input maximum

Environmental
Operating Temp. Range

–20°C to +65°C

Storage Temp. Range

–40°C to +85°C

Relative Humidity

0 to 90%, Noncondensing

IP Protection

IP20

Emissions

EN61000-6-4

Immunity

EN61000-6-2

Mechanical Dimensions (w x h x d)

0.24" x 3.67" x 4.04"

(6.2mm x 93.1mm x 102.5mm)

Housing

Terminal housing for mounting on

35mm DIN 46277

Connections

Spring cage clamp

Weight

1.6 ounces (46g)

Internal wiring

0.2 to 2.5mm

2

8mm

Spring cage clamp connection

+1

-2

+3

-4

5+

6-

7+

8-

+ -

Out

+ IN1 +

+ IN1 +

- IN1 -

- IN1 -

IN2 +

IN2 +

IN2 -

IN2 -

Expandable power-bus connector