5 primary – secondary (bi-parting) gate wiring, Primary operator secondary operator – Controlled Products Systems Group 9310-080 User Manual
Page 30

2.5 Primary – Secondary (Bi-parting) Gate Wiring
The interface wiring between the two operators requires six (6) wires (18 AWG minimum) for control
and secondary entrapment protection device connection. Each operator must be connected to it's
own power source as described in section 2.1. Be sure that both operators are wired to the same
phase in the breaker panel. Check at the breaker panel by measuring voltage from HOT to HOT.
This should read 0 volts. If the meter reads 230 Volts, change the wiring.
4403-010
Circuit Board
S
e
co
n
d
a
ry En
tr
a
p
me
n
t
P
rotec
ti
on Inpu
ts
DOORKING, INC., INGLEWOOD, CA 90301
Title:
Date:
Rev.
Dwg. No.
4403-010
Circuit Board
S
e
co
n
d
a
ry En
tr
a
p
me
n
t
P
rotec
ti
on Inpu
ts
Common
Relay
Power
Exit Loop
Reverse Loop
Reverse Loop
DoorKing
9409-010
TB1
TB2
TB3
Conduit
Primary
Operator
Secondary
Operator
Yellow
Violet
Brown
Orange
Green
Green
Yellow
Violet
Brown
Orange
A
B
C
A
Open direction non-contact sensor - Primary Operator.
C
Open direction non-contact sensor - Secondary Operator.
B
Close direction non-contact sensor - Both Operators.
Open direction contact sensor - Secondary Operator.
E
D
Open direction contact sensor - Primary Operator.
D
E
D
E
1
Connect the Primary / Secondary interconnection wiring as shown. Wire colors are based
on DoorKing interconnection cable (P/N 2600-75x).
Place a jumper from terminal 2 to terminal 4 in the PRIMARY operator only.
Set SW 1, Switch 3 to the OFF position in the PRIMARY operator.
Plug a two-channel (P/N 9409-010) loop detector into the OPEN loop port in the
PRIMARY operator. Connect loops and loop detector as shown.
Connect radio receiver as shown. If partial open feature is desired with radio receiver,
connect receiver relay to terminal 5. Connect other OPEN devices to terminal 4 (Full
Open) or terminal 5 (Partial Open) as required.
Connect standard reverse devices to terminal 6 and/or connect secondary non-contact
and/or contact sensors to Secondary Entrapment Protection inputs as shown.
2
3
4
5
1
2
3
4
5
5
5
6
Connect chassis ground to chassis ground.
6
6
7/07
A
4403-DUAL-1
Model 9310
Primary / Secondary Wiring Diagram
19
2
0
1234
56789
1
0
1
1
1
2
1
3
1
4
15
16
17
18
19
2
0
1234
56789
1
0
1
1
1
2
1
3
1
4
15
16
17
18
Open Photo
Close Photo
Open Edge
Close Edge
Common
Common
Open Photo
Close Photo
Open Edge
Close Edge
Common
Common
Page 30
9310-065-J-10-11