Exp-2000 r – Controlled Products Systems Group EXP-2000 User Manual
Page 5
1
Page 5 of 7
EXP-2000 R Electrical Connections
J1 Connections
2 - 8 to 16 VDC !
Power IN (+)
1 - Ground!
!
Power IN (-)
J2 Connections
8 - RS485 (+)!!
RS-485 Input
7 - RS485 (-)! !
RS-485 Input
6 - +5 VDC OUT!
5 Volt Power out
5 - Relay #4! !
Analog Input #4
4 - Relay # 3 !
Analog Input #3
3 - LED I/O! !
LED Signal Output
2 - Data 1 In! !
Wiegand Data 1 Input
1 - Data 0 In! !
Wiegand Data 0 Input
J3 Connections
12 - Relay #2!!
N.O. Contact
11 - Relay #2!!
Common
10 - Relay #2!!
N.C. Contact
9 - Relay #1! !
N.O. Contact
8 - Relay #1! !
Common
7 - Relay #1! !
N.C. Contact
6 - RS232 Output !
Serial Data OUT
5 - RS232 Input !
Serial Data IN
4 - Ground!
!
Wiegand/RS232 Ground
3 - Aux in!
!
Digital Input
2 -!
!
!
Not used
1 - !
!
!
Not used
DIP Switch Address Settings
ADDRESS! !
SWITCH!
!
!
!
12345678
1!
!
!
00000001
2!
!
!
00000010
3!
!
!
00000011
4!
!
!
00000100
5!
!
!
00000101
6!
!
!
00000110
7!
!
!
00000111
8!
!
!
00001000
9!
!
!
00001001
10!
!
!
00001010
11!
!
!
00001011
12!
!
!
00001100
13!
!
!
00001101
14!
!
!
00001110
15!
!
!
00001111!
16!
!
!
00010000
1 2 3 4 5 6 7 8
On
Off
Address settings for the EXP-2000
Cypress Suprex® systems will support different numbers
of additional EXP-2000 units depending upon the model
number. Refer to the specific documents for the
SPX-7400, SPX-5600, or SPX-7200 for maximum ratings.
Note:
To operate as a "Remote" unit, DIP Switch #2 must be Off.
*
J1
J2
J3
2- 8 to 16 VDC In
1- Ground
.
12- R2 N.O.
11- R2 Com
10- R2 N.C
9- R1 N.O.
8- R1 Com
7- R1 N.C.
6-RS232 output
5-RS232 Input
4-Ground
3- Aux in
2- Not used
1 - Not used
8-RS485 (+
)
7-RS485 (-)
6-+5 VDC Out
5- R4 in
4- R3 in
3-LED out
2-Data 1 in
1-Data 0 in
EXP-2000
R