Gas and steam, Electric – 30 kw, Electrical service specifications – American Dryer Corp. AD-758DV User Manual

Page 23: A. gas and steam models only

background image

113372-7

Telephone: 01422 822282

19

2. Electrical Service Specifications

IMPORTANT: Figures shown are for non-reversing models only. For reversing models contact the

factory.

a. Gas and Steam Models Only

Gas and Steam

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT:

NOTES: A.

B.


C.

208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering,
specify exact voltage.

When fuses are used they must be dual element, time delay, current

limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse value,
by applying either local and/or National Electrical Codes to listed
appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type ONLY.
For others, calculate/verify correct breaker size according to appliance
amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.

SERVICE

VOLTAGE

PHASE

WIRE

SERVICE

APPROX.

AMP DRAW

CIRCUIT

BREAKER

60 Hz

50 Hz

120

2

13.0

20

208

2

7.6

15

220

2

7.3

8.6

15

230

2

8.0

15

240

2

7.0

15

208

3

4.7

15

230

3

4.7

15

240

3

4.9

15

380

3

2.9

15

380 / 416 3ш

4

*

— 3.1 15

400 3ш

4

*

— 3.2 15

460 / 480

3

2.8

15

Electric – 30 kW

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT:

NOTES: A.

B.


C.

208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering,
specify exact voltage.

When fuses are used they must be dual element, time delay, current

limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse value,
by applying either local and/or National Electrical Codes to listed
appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY. For others,
calculate/verify correct breaker size according to appliance amp draw
rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.

SERVICE

VOLTAGE

PHASE

WIRE

SERVICE

APPROX.

AMP DRAW

CIRCUIT

BREAKER

60 Hz

50 Hz

208

3

91

125

230

3

83

125

240

3

79

100

380

3

48

60

380 3ш

4

*

— 54 70

400 3ш

4

*

— 51 70

416 3ш

4

*

— 50 70

460

3

40

50

480

3

39

50

575

3

33

50

*

3-Wire is available.

12/18/06

*

3-Wire is available.

12/18/06

b. Electric Models Only

ALL electrically heated dryers must be connected to the electric service shown on the dryer’s data
label. The connecting wires must be properly sized to handle the rated current.