7 control parameter, 1 factor polymer dosing, 2 polymer concentration – Hach-Lange RTC112 SD-Module User Manual
Page 30: 3 manual polymer dosing, 4 manual feed flow, 5 max decrease closed l, 6 max increase closed l, 7 set-point tss
30
Parameterization and operation
4.7
CONTROL PARAMETER
4.7.1
FACTOR POLYMER DOSING
Required specific polymer dosing [g/kg]. This parameter
determines how many grams of polymer per kilogram of TSS are
fed by the system.
4.7.2
POLYMER CONCENTRATION
Polymer concentration [g/L] fed via the polymer pump.
4.7.3
MANUAL POLYMER DOSING
The RTC outputs the polymer dosing rate [L/h] if
•
FEED FLOW CONTROL is activated
•
No open-loop control mode (
activated
•
The TSS measurement from the influent reports an error, or
•
The flow measurement from the influent reports an error.
4.7.4
MANUAL FEED FLOW
The RTC outputs the feed flow rate [m
3
/h] if
•
POLYMER DOSING CONTROL is activated
•
No open-loop control mode (
activated
•
The TSS measurement at the inlet reports an error, or
•
The flow measurement from the influent reports an error.
4.7.5
MAX DECREASE CLOSED L
This value defines the maximum decrease of the specific polymer
dosing rate FACTOR POLYMER DOSING [g/kg] if
CLOSED-LOOP EFFLUENT CONTROL is selected.
4.7.6
MAX INCREASE CLOSED L
This value defines the maximum increase of the specific polymer
dosing rate FACTOR POLYMER DOSING [g/kg] if
CLOSED-LOOP EFFLUENT CONTROL is selected.
4.7.7
SET-POINT TSS
Required setpoint of the TSS concentration in the dewatered
sludge.
Note: · This parameter is only considered if CLOSED-LOOP EFFLUENT
CONTROL (
) is activated.