Parameterization and operation – Hach-Lange RTC112 SD-Module User Manual
Page 23

23
Parameterization and operation
MAX DECREASE CLOSED 
L
This value defines the maximum decrease of the specific 
polymer dosing rate FACTOR POLYMER DOSING [g/kg] if 
CLOSED-LOOP EFFLUENT CONTROL is selected.
g/kg
MAX INCREASE CLOSED L
This value defines the maximum increase of the specific 
polymer dosing rate FACTOR POLYMER DOSING [g/kg] if 
CLOSED-LOOP EFFLUENT CONTROL is selected.
g/kg
SET-POINT TSS
Required setpoint of the TSS concentration in the thickened 
sludge. 
Note: This parameter is only considered if CLOSED-LOOP 
EFFLUENT CONTROL is activated.
g/L
P GAIN TSS
Proportional gain for the PID closed-loop controller for the TSS 
concentration in the thickened sludge. 
Note: This parameter is only considered if CLOSED-LOOP 
EFFLUENT CONTROL is activated.P GAIN TSS [L/g] is divided 
by 100 before it is multiplied by the deviation of the actual TSS 
concentration [g/L] from the required TSS setpoint [g/L] . 
L/g
INTEGRAL TIME TSS
Integral time for the PID closed-loop controller for the TSS 
concentration in the thickened sludge.
Note: This parameter is only considered if CLOSED-LOOP 
EFFLUENT CONTROL is activated. INTEGRAL TIME TSS is set 
to "0" to deactivate the integral part of the PI open-loop 
controller.
min
DERIVATIVE TIME TSS
Derivative time for the PID closed-loop controller for the TSS 
concentration in the thickened sludge. 
Note: This parameter is only considered if CLOSED-LOOP 
EFFLUENT CONTROL is activated.
min
SET-POINT FILT
Required setpoint of the TSS concentration in the 
centrate/filtrate. 
Note: This parameter is only considered if CLOSED-LOOP 
FILTRATE CONTROL is activated.
g/L
P GAIN FILT
Proportional gain for the PID closed-loop controller for the TSS 
concentration in the centrate/filtrate.
Note: This parameter is only considered if CLOSED-LOOP 
EFFLUENT CONTROL is activated.
P GAIN FILT [L/g] is divided by 100 before it is multiplied by the 
deviation of the actual TSS concentration from the required TSS 
setpoint. 
L/g
INTEGRAL TIME FILT
Integral time for the PID closed-loop controller for the TSS 
concentration in the centrate/filtrate.
Note: This parameter is only considered if CLOSED-LOOP 
EFFLUENT CONTROL is activated. 
INTEGRAL TIME TSS is set to "0" to deactivate the integral part 
of the PID open-loop controller.
min
4.4.1
RTC112 SD-Module open and closed-loop controller (Continued)
RTC MODULES / PROGNOSYS
RTC MODULES
RTC
