Installation – Hach-Lange RTC112 SD-Module User Manual
Page 18
18
Installation
3.4
Connection to the automation unit on the plant side
The one-channel and two-channel versions of the RTC112 SD-Module are equipped with
various modules that must be connected to the plant automation system.
•
The feed flow rate must be provided to the RTC112 SD-Module as a 0/4 to 20 mA
signal.
•
The polymer flow rate must be provided (on both versions) to the RTC112 SD-Module
as a 0/4 to 20 mA signal.
•
The polymer pump can be operated in pulse/pause mode (PWM).
•
The status signals and fault indications are output as 0 V/24 V signals.
•
Measurement errors are shown 5 minutes after the error occurs. In the event of a new
startup (return of power supply), the unit is set back to ON (24 V) after approximately
1 minute and 40 seconds if there are no measurement errors.
•
In the event of a new startup (return of power supply), the RTC operating signal is set
back to ON (24 V) after approximately 1 minute and 25 seconds.
Table 3 Connections for the 1-channel RTC112 SD-Module
Module
Name
Connection Signal
Function
4x digital output
1
KL2134
1
+24 V/0 V
Polymer pump on/off (24 V/0 V); (LED a)
5
+24 V/0 V
Closed-loop control of the feed flow rate
active/inactive (24 V/0 V); (LED c)
4
+24 V/0 V
Input signals OK (24 V), input signal faulty (0 V);
(LED b)
8
+24 V/0 V
RTC operational (24 V), RTC faulty (0 V), (LED d)
2x analog output
KL4012
1(+) - 3(-)
0/4 to 20 mA
Output of the polymer pump flow rate
5(+) - 7(-)
0/4 to 20 mA
Output of the feed flow rate
1x analog input
KL3011
1(+) - 2(-)
0/4 to 20 mA
Input of the feed flow rate
1x analog input
KL3011
1(+) - 2(-)
0/4 to 20 mA
Input of the polymer flow rate
Bus termination
KL9010
Bus termination
1
Ground to connection 3 and 7 or to the supply voltage connections
Table 4 Connections for the 2-channel RTC112 SD-Module
Module
Name
Connection Signal
Channel
Function
8x digital
output
1
KL2408
1
+24 V/0 V
1
Polymer pump on/off (24 V/0 V) (LED a)
5
+24 V/0 V
1
Closed-loop control of the feed flow rate
active/inactive (24 V/0 V) (LED e)
2
+24 V/0 V
1
Input signals OK (24 V), input signal faulty (0 V)
(LED b)
6
+24 V/0 V
1
RTC operational (24 V), RTC faulty (0 V) (LED f)
3
+24 V/0 V
2
Polymer pump on/off (24 V/0 V) (LED c)
7
+24 V/0 V
2
Closed-loop control of the feed flow rate
active/inactive (24 V/0 V) (LED g)
4
+24 V/0 V
2
Input signals OK (24 V), input signal faulty (0 V)
(LED d)
8
+24 V/0 V
2
RTC operational (24 V), RTC faulty (0 V) (LED h)
2x analog
output
KL4012
1(+) - 3(-)
0/4 to 20 mA
1
Output of the polymer pump flow rate
5(+) - 7(-)
0/4 to 20 mA
1
Output of the feed flow rate