Page 25: 21 b. electric models only

background image

21

b. Electric Models Only

IMPORTANT: Figures shown are for non-reversing models only. For reversing models contact the

factory.

IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is

affixed to the left side panel/wall area behind the control door. In the case of 208

VAC or 240 VAC, the supply voltage must match the electric service specifications

of the data label exactly.

IMPORTANT: The wire size must be properly sized to handle the related current.

WARNING: 208 VAC AND 240 VAC ARE NOT THE SAME. Any damage done to dryer

components due to improper voltage connections will automatically VOID THE

WARRANTY.

NOTE: ADC reserves the right to make changes in specifications at any time without notice or

obligation.

IMPORTANT: 3-phase (3ø) figures shown are for a 3-wire service only.

APPROX.

AMP

DRA

W

M LE-75 (E

LECTRIC

)

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT: 208 VAC and 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.

NOTES:

A. Fuse ratings are dual element, time delay, current limiting, class RK1 or RK5 ONLY.
B. Circuit breakers are thermal/magnetic (industrial) motor curve type ONLY. For others, calculate/verify correct breaker size according to appliance amp draw

rating and type of breaker used.

C. Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.

APPLIED VOLTAGE/PHASE

KW

208/1ø (60 Hz)

240/1ø (60 Hz)

208/3ø (60 Hz)

240/3ø (50/60 Hz)

380/3ø (50 Hz)

416/3ø (50 Hz)

460/3ø (60 Hz)

20

104

90

---

---

33

---

---

24

---

---

72

63

---

36

33

30

---

---

88

77

---

45

41

33

---

---

---

---

53

---

---

36

---

---

105

92

---

53

48

40

---

---

---

---

---

59

---