English – Burkert Type TAT002 User Manual
Page 11

0911 - 9
english
Alarms
ALH
Hysteresis for the
Automatic alarm acknowledgement:
Limit value alarms
With high alarm undershot by
ALL and ALU
ALU - ALH and with low alarm with
under shooting of ALL + ALH
(0.1 K...upper measurement range)
dAO
Alarm delay at
0...23.5 hours; suppression of
with Mains ON
Alarms after commissioning.
S01
Status of the control relay
oFF = opened
with sensor fault
on = closed
tbA
Status of the control relay
oFF = Relay deactivated
after acknowledgement (by
on = Relay activated
(any button) in an
alarm situation
AS
Configuration of the alarm
cL = Terminal 4-5 closed
relay at an alarm
oP = Terminal 4-6 closed
Measured value display
LCI
Lower analog
Lower display value for current input
Display value
4 mA or with voltage input 1 V
(-1999...1999)
or 10 V (only for inputs 4-20
mA, 0-1V, 0-10 V)
UCI
Upper analog
Upper display value for current input
Display value
20 mA or for voltage input 1 V or 10 V
(-1999...1999)
(only for the 4-20 mA, 0-1V, 0-10 V
inputs)
OPb
calibration of the sensor
regardless of the measurement range
rES
Resolution
in = only whole numbers
dE = also tenths
ce = hundreths
UdM
Units
Display of the units directly in the
illuminated display. Regardless of which
controller type is being used:
see
General description
PbC
Type of sensor
Type of inout
Temperature sensor U):
J = Thermoelement „J“; Pt = Pt100;
C = Thermoelement „K“; Ptc = PTC;
S = Thermoelement „S“; ntc = NTC
Current / voltage input
cur = 4...20 mA; 0-1 = 0...1 V;
(AU)
10 = 0...10 V
P3F
Third terminal of a
(if present)
Pt100 sensor
no = Pt100 2-wire wired
yES = Pt100 3-wire wired