English, 4 parameters – Burkert Type TAT002 User Manual
Page 10

8 - 0911
english
2.4
Parameters
Control
Hy1
Hysteresis 1
Switch hysteresis of Set-value 1 with
positive or negative values. The default
range is dependent on the input type.
The parameter may not be entered as
zero.
LS1
Lowest set-value setting
Set-value limits for operator
US1
Highest set-value setting
Set-value limits for operator
S1C
control effect
in = inverse (heating, humidification)
dir = direct (cooling, dehumidification)
AC
Minimum switch duration
0...250 sec relay switch-off duration
on
Minimum switch-on period
0...250 sec relay switch-on period
ono
Minimum delay
0...120 min; minimum delay between two
activations of the control relay.
Alarms
ALC
Configuration
rE = relative to the set-value (in Kelvin)
Temperature alarm
Ab = absolute values (in °C)
ALL
Low temperature alarm
If SET - ALL is undershot,
a low temperature alarm will be triggered
after the delay time ALd.
ALU
Over-temperature alarm
If SET + ALU exceeded, a high
temperature alarm will be triggered after
delay time ALd.
ALd
Alarm delay
0...999 min; Minimum time in which the
at temperature
conditions for an alarm situation
Overshoot/Undershoot
must be present.
Sensor
Lower limit
Upper limit
NTC
-40°C
110°C
PTC
-50°C
150°C
Pt100
-200°C
600°C
TcK
0°C
1300°C
TcJ
0°C
600°C
TcS
0°C
1400°C
MEASUREMENT LIMITS FOR THE SENSOR TYPES