Commander LI90 Series

Appendix

Simulation Mode
This mode enables the end user to simulate changes in level without having the level of liquid
move. The display will simulate level of liquid and will turn the relays ON and OFF according
to how they were configured. For example, if Relay 1 is set as a Pump Empty with an ON
setting for 100.0 inches and an OFF setting of 30.0 inches, then when the display goes above
100.0, Relay 1 will energize and when the level falls below 30.0, Relay 1 will de-energize. This
function can be used to test the wiring and to verify if the configuration is set accordingly.

Please note: Simulation mode will energize and de-energize all configured relays. Any devices
wired to the relays will become active during simulation mode. To turn off individual relays,
Select OFF in the H.O.A. section before entering the Simulation mode.

• Simulation Mode I sunder the secured section of the display

o

To access this function, press and hold the ENTER key for 5 seconds. The
display will jump to the configuration section.

o

Once in the Secured Function Section, press the Simulation Mode soft key