Flowline LI90 Commander User Manual
Page 27

27 AUG 08
PRELIMINARY MANUAL
27 of 57
Rev 1_3
Commander LI90 Series
• Configuration of Outputs
o
Once in the Secured Function Section, press the Config Outputs soft key
o
Each relay will ask for a Relay ON and Relay OFF level. These settings must be
in the same units used for the Empty and Full settings
Relay ON
Relay OFF
• If you are reading between 0 to 500 gallons, then the relay set points must
be in gallons
• For Pumps and Valves, use both settings as the ON/OPEN and
OFF/CLOSE points for the device
• For Alarms, use the ON point where the relay will start and the OFF as a
hysteresis to prevent chattering of the relay
High Alarm
Low Alarm
Automatic Fill
Automatic Empty
o
To change a value, first press the Enter key
• The value will be highlighted
• Use the 10-digit keypad to enter the desired value
• I.e. for 123.4, press the following keys:
• Press Enter when completed to store this value to memory