Step Six 

How to select the correct pressure transmitter? 
The objective is to select a sensor with an operational range that will cover the entire application span.  If the 
liquid  height  of  the  tank  is  above  the  sensor’s  Maximum  Liquid  Height,  then  the  sensor  will  not  be  able  to 
read  a  full  tank  level.    Compare  the  tank’s  Pressure  @  Full  against  the  sensor’s  pressure  range  to  select  a 
sensor. 

To calculate the tank’s Pressure @ Full, use the following formula: 

Pressure @ Full = [Height @ Full Tank (feet) x SG] / 2.31 (feet/psi) 

Pressure @ Full = [Height @ Full Tank (meters) x SG] / 0.704 (m/psi) 

To select the correct pressure transmitter, follow the steps below: 

1. Measure the Height @ Full Tank (in feet or meters). 

2. Determine the SG for the liquid (if the customer does not know, check the MSDS sheet). 

3. Use the formula above to calculate the Pressure @ Full.  

a. Example:  A 16’ tank with a liquid media SG of 0.9 has a Pressure @ Full of 6.23 psi. 

b. [(16’ x 0.9) / 2.31’/psi] = 6.23 psi 

4. Select a pressure transmitter with a pressure greater than or equal to the Pressure @ Full

a. In the example above for a 16’ tall tank with a SG=0.9, you need a pressure range greater than 

or equal to 6.23 psi. 

b. Using  a  sensor  with  a  pressure  range  of  15  psi  provides  a  Maximum  Liquid  Height  of  38.5’, 

which will read the entire range of the 16’ tall tank. 

c. Using  a  sensor  with  a  pressure  range  of  5  psi  provides  a  Maximum  Liquid  Height  of  12.83’, 

which is short by 3.17’. 

i. This  means  that  the  sensor  will  output  20  mA  at  12.83’  of  liquid  and  the  top  3.17’  of 

liquid will not be measured.