Technical specifications, 7 technical specifications, 1 technical specifications – DE DIETRICH VIVADENS MCR-P 24_28 BIC User Manual
Page 27
7 Technical specifications
7.1
Technical specifications
MCR-P BIC
Boiler
Heating mode
Nominal useful output 40/30 (min / max)
kW
6.3 /25.3
Nominal useful output 80/60 (min / max)
kW
5.5 / 23.6
Nominal input power
kW
24
Minimum input power
kW
5.8
Domestic hot water mode
Nominal useful output
kW
27.4
Nominal input power
kW
28
Minimum input power
kW
5.8
Gas flow rate at nominal output (15 °C -
1013 mbar)
Natural gas H (G20)
m
3
/h
2.4
Propane (G31)
Kg/h
1.9
LHV efficiency
100% of nominal output and average water
temperature in the boiler of 70°C
%
98.3
LHV efficiency
100% of nominal output and return temperature of
30°C
%
104.4
LHV efficiency (92/42/EEC Gas Appliance
Directive)
30% of nominal output and return temperature of
30°C
%
108.7
HHV efficiency
100% of nominal output and average water
temperature in the boiler of 70°C
%
88.5
HHV efficiency
100% of nominal output and return temperature of
30°C
%
94
HHV efficiency (92/42/EEC Gas Appliance
Directive)
30% of nominal output and return temperature of
30°C
%
97.9
Maximum temperature (Safety thermostat cut-off)
°C
110
Stand-by losses (ΔT = 30 °C)
W
30
Losses through the outer casing
%
1.1
Water content
litres
1.8
Weight empty, without mounting frame, without front cover
kg
61
Heating circuit
Nominal water flow (ΔT = 20 K)
m
3
/h
1.03
Manometric height (ΔT = 20 K)
mbar
(1)
> 200
Flow temperature
°C
75
Maximum pressure
bar
3
Expansion vessel
litres
8
Initial pressure of the expansion vessel
bar
1
Minimum operating pressure
bar
0.8
Domestic hot water circuit
Instruction set outlet temperature
°C
60
Specific hot water flow (ΔT = 30 K)
(2)
litres per min. 18
Nominal max cold water pressure
(2)
bar
8
Minimum pressure for 11 l/min
(2)
bar
0.5
(1) 1 mbar = 100 Pa, 1 daPa = 1 mmWG
(2) Cold water inlet temperature: 10 °C
MCR-P 24/28 BIC
7. Technical specifications
060513 - 127686-01
26