Code

Cause of
the fault

Description

Checking / solution

e11

PCU

Difference between the flow and

return temperatures too great

Bad connection

Sensor fault

4

Contact the professional who takes care of maintenance of the

appliance

No water circulation

4

Vent the air in the heating system

4

Check the circulation (direction, pump, valves)

4

Check the water pressure

e12

PCU

Maximum boiler temperature

exceeded (STB thermostat

maximum)

Bad connection

Sensor fault

4

Contact the professional who takes care of maintenance of the

appliance

No water circulation

4

Vent the air in the heating system

4

Check the circulation (direction, pump, valves)

4

Check the water pressure

e14

PCU

5 burner start-up failures

No ignition

4

Contact the professional who takes care of maintenance of the

appliance

Ignition arc, but no flame formation

4

Check that the gas valve is fully opened

4

Contact the professional who takes care of maintenance of the

appliance

Presence of the flame but insufficient ionization (<3 µA)

4

Check that the gas valve is fully opened

4

Contact the professional who takes care of maintenance of the

appliance

e16

PCU

Detection of a parasite flame

Ionization current present even though there is no flame

Ignition transformer defective

Gas valve defect

The burner remains very hot: CO

2

too high

4

Contact the professional who takes care of maintenance of the

appliance

e17

PCU

Internal error on the SU board

Bad connection

SU PCB faulty

4

Contact the professional who takes care of maintenance of the

appliance

e34

PCU

The fan is not running at the right

speed

Bad connection

Fan defective

4

Contact the professional who takes care of maintenance of the

appliance

e35

PCU

Flow and return reversed

Bad connection

Sensor fault

4

Contact the professional who takes care of maintenance of the

appliance

Water circulation direction reversed

4

Check the circulation (direction, pump, valves)

e36

PCU

The flame went out more than 5

times in 24 hours while the burner

was operating

No ionization current

4

Check that the gas valve is fully opened

4

Contact the professional who takes care of maintenance of the

appliance

EGC 25

6. Troubleshooting

03/12/2013 - 300026082-001-02

26