2 c 610 eco – DE DIETRICH C 310 ECO - C 610 ECO User Manual
Page 17

17
02/10/07 - 300015183-001-A
C 310 ECO - C 610 ECO
7.2 C 610 ECO
C 610-... ECO
Unit
700
860
1000
1140
Introduction
Number of sections
2 x 6
2 x 7
2 x 8
2 x 9
Regulating the output
Modulating
Output (80/60°C) PN
minimum
kW
87
123
122
148
maximum
kW
654
790
924
1062
Output (50/30°C) PN
minimum
kW
94
131
130
156
maximum
kW
706
854
998
1146
Nominal output (Hi)
minimum
kW
91
128
127
153
maximum
kW
672
808
942
1078
Combustion gas and by-products
Gas category
(see table in "General Description" chapter)
Gas supply pressure
mbar
17 - 25
Gas flow rate Gas H/E (15°C - 1013 mbar)
minimum
m
3
/h
9.6
13.5
13.4
16.2
maximum
m
3
/h
70
85.4
99.6
114
Gas flow rate Gas L/LL(15°C - 1013 mbar)
minimum
m
3
/h
11.2
15.8
15.6
18.8
maximum
m
3
/h
82.6
99.4
115.8
132.6
Average nitrogen oxide emission (NOx)
mg/kWh
< 60
Maximum pressure at the flue gas nozzle
Pa
130
Combusted gas flow
minimum
kg/h
153
215
214
257
maximum
kg/h
1130
1360
1586
1814
Temperatures of the combusted gases at 80/
60°C
minimum
°C
57
maximum
°C
65
Boiler types:
B23, C33, C53, C63, C83
Heating
Safety temperature
°C
110
Water setting range
°C
20 - 90
Water pressure minimum
bar
0,8
Water pressure maximum
bar
6
Water content
l
120
142
164
186
Water resistance at
∆
T = 10°C
mmCE
4400
4800
4400
5000
Water resistance at
∆
T = 20°C
mmCE
1100
1200
1100
1250
Electricity characteristics
Power supply voltage
V/Hz
230 / 50
Power consumption
minimum
W
12
maximum
W
694
980
1240
1684
Insulation class
IP
21
Miscellaneous
Weight without water
kg
820
920
1020
1120
Acoustic level at 1 meter
dBA
63