Dynasonics PFP-600 User Manual
Page 13

units = 5-8, and 10
pipe ID range is 102 mm. - 1524 mm.
To set high alarm (RELAY-2), press “HIGH ALARM” key. The
µP display will show
“ALARM HIGH”. Use the “SCROLL” keys to increase or decrease value. The default
value is 20.00. When finished, press “ENTER” key to exit.
units = 1-4
high alarm range is 0.00” - 60.00”
units =5-8
high alarm range is 0.00 - 6.08 MPS
units =9
high alarm range is 0.00” - 60.00”
units = 10
high alarm range is 0.00 cm. - 152.00 cm.
To set low alarm (RELAY-1), press “LOW ALARM” key. The
µP display will show
“ALARM LOW”. Use the “SCROLL” keys to increase or decrease value. Default value
is 00.00. When finished, press “ENTER” key to exit.
units = 1-4 (flow)
low alarm range is 0.00 - 20.00 FPS
units = 5-8 (flow)
low alarm range is 0.00 - 6.08 MPS
units = 9 (level)
low alarm range is 0.00” - 60.00”
units = 10 (level)
low alarm range is 0.00 cm. - 152.00 cm.
Totalizer operation display with or without multiplier
units = 2 - 4
totalizer range is 0 - 99999999 GALS (GALLONS)
units = 6 - 8
totalizer range is 0 - 99999999 LTRS (liters)
11